Mount the 1797-PS2E2 Power Supply
Follow these directions to properly install the 1797-PS2E2 power supply. Refer to the Installation and Commissioning section, page 7, for important precautions and considerations.
Rockwell 1797-PS2E2 IS Module Type Power Supply
1. Overview of 1797-PS2E2 Power Supply:
- The 1797-PS2E2 is a 24V dc in/quad-Ex dc out power supply enclosed in a flame-proof enclosure with increased safety input and output terminations.
- Specifics:
- 24V dc gland (M20 x 1.5) for cables of 6-12 mm diameter.
- Ex outputs (M16 x 1.5) for cables of 4-8 mm diameter.
- Features include 24V dc supply source, four channels with 8.5 W output each, dual power feeds for source input redundancy, and galvanic isolation of outputs from the source.
2. Understanding System Planning:
- System planning involves determining module requirements, power supply needs, system partitioning, and cabinet placement.
- Example: Using a fiber hub requiring 8.5 W, 11 IS-power outputs are needed, and three power supplies are sufficient, each providing four independent IS-power outputs at 8.5 W.
3. Role of Power Supply in Intrinsically Safe Systems:
- The power supply is a crucial component in an intrinsically safe system.
- It isolates unsafe incoming power, limiting energy to IS-safe levels.
- FLEX Ex modules in hazardous areas derive power for valves, actuators, or transmitters from the power supply.
4. Installation and Commissioning:
- Location and Zones:
- The power supply can be located in Zones 1, 2, and 22 as labeled.
- Output circuits are Ex ib, suitable for installation in Zones 1, 2, and 22.
- Installation Guidelines:
- Follow EC-type examination certificate and national regulations.
- Housing (Ex d) must not be opened; connections in (Ex e) terminal box.
- Power feed lines installed in the deenergized state.
- Safety Measures:
- Intrinsically-safe output terminals can be connected and disconnected during operation.
- Unused cable glands covered with Ex e lead seals (IP54).
- Inspection and replacement of damaged seals before closing (Ex e) wiring box.
- Earthing and Fixing:
- (Ex d) housing includes earthing screw (connected to Earth with a minimum 4 mm² area).
- Two flanges for secure fixing to a wall or structural part.
- Maintenance and Cleaning:
- (Ex e) terminal box can be opened for maintenance, ensuring dust-free conditions.
By organizing the information in this manner, the article provides a structured understanding of the 1797-PS2E2 power supply, its role in system planning, installation guidelines, and crucial safety measures for intrinsically safe systems.