GDD360C 3BHE047217R0101 Power Module
GDD360C 3BHE047217R0101 CT-S Range Technical Data:
Input Circuit – Supply Circuit:
- Rated Control Supply Voltage:
- CT-xxx.x1: 24-240 V AC/DC
- CT-xxx.x2: 24-48 V DC, 24-240 V AC
- CT-xxx.x3: 380-440 V AC
- Rated Control Supply Voltage Tolerance: -15% to +10%
- Rated Frequency: DC or 50/60 Hz (AC)
- Frequency Range: 47-63 Hz (AC)
- Typical Power Consumption: Max. 16 VA
- Power Failure Buffering Time:
- 24 V DC: Min. 15 ms
- 230/400 V AC: Min. 20 ms
- Release Voltage: > 10% of the minimum rated control supply voltage Us
- Minimum Energizing Time: 100 ms (CT-ARS)
- Formatting Time: 5 min (CT-ARS)
GDD360C 3BHE047217R0101 Input Circuit – Control Circuit:
- Kind of Triggering: Voltage-related triggering
- Control Input, Control Function:
- A1-Y1/B1 start timing external (CT-MVS, CT-MXS, CT-APS)
- Y1-Z2 start timing external / X1-Z2 pause timing / accumulative functions (CT-MFS)
- Parallel Load / Polarized: Yes / No
- Maximum Cable Length to Control Input: 50 m (100 pF/m)
- Minimum Control Pulse Length: 20 ms
- Control Voltage Potential: See rated control supply voltage
- Current Consumption of Control Input:
- 24 V DC: 1.2 mA
- 230 V AC: 8 mA
- 400 V AC: 6 mA
GDD360C 3BHE047217R0101 Remote Potentiometer:
- Resistance Value: Z1-Z2: 50 kΩ (CT-MFS, CT-MBS, CT-MVS.21, CT-MXS) / Z3-Z2: 50 kΩ (CT-MXS)
- Maximum Cable Length to Remote Potentiometer: 2 x 25 m (shielded with 100 pF/m)
- Shield Connection: Z2
GDD360C 3BHE047217R0101 Timing Circuit:
- Time Ranges: 10 time ranges (0.05 s – 300 h)
- Recovery Time:
- 24-240 V AC/DC: < 50 ms
- 24-48 V DC, 24-240 V AC: < 80 ms
- 380-440 V AC: < 60 ms
- Accuracy:
- Within rated control supply voltage tolerance: < 0.004% / V
- Within temperature range: < 0.03% / °C
- Repeat Accuracy (Constant Parameters): < ±0.2%
- Setting Accuracy of Time Delay: ±6% of full-scale value
Star-Delta Transition Time:
- Fixed Time: 50 ms (CT-SDS, CT-MBS, CT-MFS, CT-MVS.2x)
- Tolerance: ±2 ms