Description
DSDI110N Verify that the relay’s nominal current of 1 A or 5 A matches the secondary rating of the
connected CTs. Unmatched CTs may result in equipment damage or inadequate
protection.
The exact placement of a zero-sequence CT so that ground fault DSDI110N current will be detected is
shown below. Twisted pair cabling on the zero-sequence CT is recommended.
Note
IMPORTANT: The relay will correctly measure up to 46 times the current input nominal
rating. Time overcurrent curves become horizontal DSDI110N lines for currents above the 46 × CT
rating.
The 745 has one voltage divider type input for AC voltages. There are no internal fuses or
ground connections. Voltage transformers up to a maximum 5000:1 ratio may be used.
The nominal secondary voltage must be in the 60 to 120 V range.
3.2.7 Logic Inputs
External contacts can be connected to the 16 logic inputs. As shown, these contacts can
be either dry or wet. It is also possible to use a combination of both contact types.
A dry contact has one side connected to terminal D11. This is the +32 V DC voltage rail. The
other side is connected to the required logic input terminal. When a dry contact closes, a
2.2 mA current flows through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power
supply. The other side is connected to the required logic input terminal. In addition, the
negative side of the external source must be connected to the relay DC negative rail at
terminal D12. The maximum external source voltage for this arrangement is 300 V DC.
Correct polarity must be observed for all logic input connections or equipment damage
may result.
The label found on the left side of the relay specifies its order code or model number. The
installed power supply operating range will be one of the following.
LO: 25 to 60 V DC or 20 to 48 V AC
HI: 88 to 300 V DC or 70 to 265 V AC
Ensure the applied control voltage matches the requirements of the relay’s switching
power supply. For example, the HI power supply will work with any DC voltage from 88 to
300 V, or any AC voltage from 70 to 265 V. The DSDI110N internal fuse may blow if the applied voltage
exceeds this range.
Control power supplied to the relay must match the installed power supply range. If the
applied voltage does not match, damage to the unit may occur.