Bently 3500/15-02-02-01 I/O Intelligent Module Monitoring System

Product name:Bently 3500/15-02-02-01 I/O Intelligent Module Monitoring System

Product model:3500/15-02-02-01

Quantity: inventory

Warranty: We provide warranty service for 3500/15-02-02-01

Shipping Port:FuJian

Product technical documents: no relevant documents

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

3500/15-02-02-01 The general approach for testing OK limits is to input a DC voltage and adjust it

above the Upper OK limit and below the Lower OK limit. This will cause a channel

not OK condition and the OK Relay to change state (de-energize). 3500/15-02-02-01 The Upper and

Lower OK limits are displayed in the Verification screen on the test computer.

 

brand Product Name Product model Order No
BENTLY modular 3500/15-02-02-01 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1806092-3929

 

  1. Disconnect PWR, COM, and SIG field wiring from the channel terminals on

the I/O module.

  1. Connect test equipment and run software as described in Section 5.1.5.5

(Test Equipment and Software Setup – Thrust Position and Differential

Expansion).

  1. 3500/15-02-02-01 Bypass all other configured channels.
  2. Adjust the power supply voltage to -7.00 Vdc.
  3. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

monitor OK LED is on and that the Channel OK State line in the Channel

Status box of the Verification screen reads OK.

  1. Verify that the OK relay on the Rack Interface I/O Module indicates OK

(energized). See 3500/20 Rack Interface Module Operation and

Maintenance Manual, part number 129768-01.

  1. Increase the power supply voltage (more negative) until the OK LED just

goes off (upper limit). Verify that the Channel OK State line in the Channel

Status box reads not OK and that the OK Relay indicates not OK. Verify

that the Upper OK limit voltage displayed on the Verification screen is

equal to or more positive than the input voltage.

  1. 3500/15-02-02-01 Decrease the power supply voltage (less negative) to -7.00 Vdc.
  2. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

OK LED comes back on, the OK relay energizes, and the Channel OK State

line in the Channel Status box reads OK.

  1. Gradually decrease the power supply voltage (less negative) until the OK

LED just goes off (lower limit). 3500/15-02-02-01 Verify that the Channel OK State line in the

Channel Status box reads not OK and that the OK Relay indicates not OK.

Verify that the Lower OK limit voltage displayed on the Verification screen

is equal to or more negative than the input voltage.

  1. Increase the power supply voltage (more negative) to -7.00 Vdc.
  2. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

OK LED comes back on, the OK relay energizes, and the Channel OK State

line in the Channel Status box reads OK.

  1. If you can not verify any configured OK limit, go to Section 5.1.10 (If a

Channel Fails a Verification Test).

  1. Disconnect the test equipment and reconnect the PWR, COM, and SIG field

wiring to the channel terminals on the Monitor I/O Module. 3500/15-02-02-01 Press the

RESET switch on the Rack Interface Module (RIM) and verify that the OK

LED comes on and the OK relay energizes.

  1. Repeat steps 1 through 14 for all configured channels.
  2. Return the bypass switch for all configured channels to their original

Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!

 

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen