3500/20 125744-02 The general approach for testing alarm setpoints is to simulate the Acceleration
signal with a function generator and power supply. The alarm levels are tested by
varying the output from the test equipment and observing that the correct results
are reported in the Verification screen on the test computer. 3500/20 125744-02 It is only necessary
to test those alarm parameters that are configured and being used. The general
test procedure to verify current alarm operation will include simulating a
transducer input signal and varying this signal:
- to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints, and
- to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints, and
- to produce a nonalarm condition.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/20 125744-02 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1806092-3929 |
When varying the signal from an alarm condition to a nonalarm condition, alarm
hysteresis must be considered. 3500/20 125744-02 Adjust the signal well below the alarm setpoint for
the alarm to clear.
Direct
- Disconnect PWR / B, COM, and SIG / A field wiring from the channel
terminals on the I/O module.
- Connect test equipment and run software as described in Section 5.1.8.1
(Test Equipment and Software Setup – Acceleration). If no filtering has
been configured, leave the frequency of the function generator set to 100
Hz. If filtering is configured, 3500/20 125744-02 the needed frequency can be calculated from
the following formula:
HPF = High-pass Filter Corner Frequency
LPF = Low-pass Filter Corner Frequency
If no filtering is configured, set the frequency of the function generator to
100 Hz.
3500/20 125744-02 If a low-pass filter is configured and no high-pass filter is configured, use
the following to determine the HPF to use in the formula:
– If the units are integrated or rms, use a HPF of 10 Hz. For any other
configuration, use a HPF of 3 Hz.
If a high-pass filter is configured and no low-pass filter is configured, use
the following to determine the LPF to use in the formula:
– If the configuration is a single channel with no integration, use a
LPF of 30 kHz.
– If the configuration is a single channel with integration, use a LPF
of 14.5 kHz.
– If the configuration is a dual channel pair, use a LPF of 9.155 kHz.
Set the frequency of the function generator to this new value. 3500/20 125744-02 The above is done
to obtain a test frequency in the center of the channel frequency range.
- Adjust the function generator amplitude to produce a reading that is
below the Direct setpoint levels on the Direct bar graph display of the
Verification screen.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for Direct is green, and the Current
Value field contains no alarm indication.
- Adjust the function generator amplitude such that the signal just exceeds
the Direct Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after
the alarm time delay expires and verify that the bar graph indicator for
Direct changes color from green to yellow 3500/20 125744-02 and the Current Value Field
indicates an Alarm.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen