3500/42M General Analog Output Wiring Methods
Each output should be connected using a good quality shielded wire with the cable shield
grounded at the module end. See Chapter 9 for more information.
Using Generic Terminal Block or Strip
Mount a terminal strip inside the control 3500/42M enclosure and run a shielded cable from the
terminal strip to each output circuit on the module’s terminal board terminals.
Ground each cable’s shield at the module end to a single GND terminal on the module’s
terminal board. 3500/42M Connect each cable shield to its own terminal on the terminal strip.
Wire the field device to the terminal strip with shielded cables, connecting each shield to
the terminal that has the corresponding shield for the cable that connects to the module
terminal board. Using this arrangement, the shields are “carried through” the terminal
strip. (This is illustrated in the section “ Analog Output Shield Grounding Example
Three.”) Also, keep the length of exposed (outside of shield) leads at the terminal strip and
device ends as short as possible.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/42M | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
3500/42M Direct Method
Run a shielded cable from each field device (transducer, potentiometer, etc.) directly to the
module.
Connect the conductors to the applicable screws on the module’s terminal board.
Ground the shield at the module end only, 3500/42M exposing a minimum amount of conductor to the
noisy environment. Do not connect the shield at the device end (cut shield off at device
end of cable and insulate with shrink tubing).
TBQC Not Recommended for Analog Modules
The Terminal Block Quick Connect (TBQC) Assembly is not recommended for use with analog
modules due to cable shielding requirements.
For analog output modules, the shield is normally grounded at only the source end (the module)
as shown in Figure 3-9. The GND connection provides access to the baseplate (frame ground)
resulting in superior rejection of noise caused by any shield drain currents. In extreme noise
environments, you can connect a ground braid from the GND terminal to an external earth
ground to bypass noise around the module (see “Analog Output Shield Grounding Example
Two”)
3500/42M If using a terminal strip between the analog output module and the field devices (user loads),
use the method in the following figure for grounding the cable shields. Note that each cable is
only grounded at one end – the end closer to the Analog Output Module. An optional external
ground connection to the output module’s GND terminal is shown for installations that require
extra noise suppression.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen