Description
3500/53M The Proximitor/Seismic Monitor supports two module software switches and four
channel software switches. These switches let you temporarily bypass or inhibit
monitor and channel functions. 3500/53M Set these switches on the Software Switches
screen under the Utilities Option on the main screen of the Rack Configuration
Software.
A switch that allows the monitor to be configured. To configure the monitor,
enable () this switch and set the key switch on the front of the Rack
Interface Module in the PROGRAM position. When downloading a
configuration from the Rack Configuration Software, 3500/53M this switch will
automatically be enabled and disabled by the Rack Configuration Software.
If the connection to the rack is lost during the configuration process, use this
switch to remove the module from Configuration Mode.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/53M | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
Channel Switches
3500/53M Alert Bypass
When enabled, the channel does not perform Alert alarming functions.
Danger Bypass
When enabled, the channel does not perform Danger alarming functions.
Special Alarm Inhibit
When enabled, all nonprimary Alert alarms are inhibited.
Bypass
When enabled, 3500/53M the channel provides no alarming functions and supplies no
proportional values.
The channel switch number is used in the Communication Gateway and Display
Interface Modules.
The Proximitor/Seismic I/O Module receives signals from the transducers and
routes the signals to the Proximitor/Seismic Monitor. The I/O module supplies
power to the transducers. The I/O module also provides a 4 to 20 mA recorder
output for each transducer input channels. Only one I/O module can be installed
at any one time and must be installed behind the monitor (in a rack mount or
panel mount rack) or above the monitor (in a Bulkhead rack).
3500/53M This section describes how to use the connectors on the I/O modules, lists what
cables should be used, and shows the pin outs of the cables. The 3500 Field
Wiring Diagram Package (part number 130432-01) shows how to connect
transducers and recorders to the I/O module or the External Termination Block.
The Internal Barrier I/O modules requires that each transducer be connected to the Barrier
I/O module individually. This module provides four channels of intrinsically safe signal
conditioning for Proximitor and/or Seismic transducers and has two internally mounted
zener barrier modules, one for each pair of transducer channels. There are three types of
Internal Barrier I/O Module; the first variant provides four channels for Proximitor
transducers only, the second provides two channels for Proximitor transducers and two for
Seismic transducers, 3500/53M and the third provides four channels for Seismic transducers only. A
3500 Earthing Module is required for systems that use Internal Barrier I/O Modules to
provide an intrinsically safe earth connection for intrinsically safe applications. Refer to the
Rack Installation and Maintenance Manual for system requirements when using Internal
Barrier I/O Modules.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 181 0693 7731
Mail: 2872270648@qq.com
Contact: Chen