3500/65-01-00 The following sections describe how to test alarms, verify channels, and test OK

limits for channels configured as Eccentricity. The output values and alarm

setpoints are verified by varying the input Eccentricity 3500/65-01-00 signal level (both peak to

peak amplitude and DC voltage bias) and observing that the correct results are

reported in the Verification screen on the test computer.

 

brand Product Name Product model Order No
BENTLY modular 3500/65-01-00 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1810693-7731

 

3500/65-01-00 The general approach for testing alarm setpoints is to simulate the eccentricity

signal with a function generator and power supply. The alarm levels are tested

by varying the output from the test equipment and observing that the correct

results are reported in the Verification screen on the test computer. It is only

necessary to test those alarm parameters that are 3500/65-01-00 configured and being used.

The general test procedure to verify current alarm operation will include

simulating a transducer input signal and varying this signal:

    1. to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
    2. to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
    3. to produce a nonalarm condition.

3500/65-01-00 Peak to Peak

  1. Disconnect PWR, COM, and SIG field wiring from the channel terminals on

the I/O module.

  1. Connect test equipment and run software as described in Section 5.1.7.1

(Test Equipment and Software Setup – Eccentricity).

  1. Adjust the function generator amplitude such that 3500/65-01-00 the signal level does not

exceed any setpoint value for the pp mil bar graph.

  1. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

OK LED is on, the bar graph indicator for pp is green, and the Current Value

field has no alarm indication.

  1. 3500/65-01-00 Adjust the function generator amplitude such that the signal just exceeds the

pp Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the alarm

time delay expires and verify that the bar graph indicator for pp changes color

from green to yellow and that the Current Value Field indicates an Alarm.

  1. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

bar graph indicator for pp remains yellow and that the Current Value Field still

indicates an Alarm.

  1. 3500/65-01-00 Adjust the function generator amplitude such that the signal just exceeds the

pp Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the

alarm time delay expires and verify that the bar graph indicator for pp

changes color from yellow to red and that the Current Value Field indicates

an Alarm.

  1. Press the RESET switch on the Rack 3500/65-01-00 Interface Module (RIM). Verify that the

bar graph indicator for pp remains red and the Current Value Field still

indicates an Alarm.

  1. Adjust the function generator amplitude such that the signal reads below the

Over Alarm setpoint levels. If the nonlatching option is configured, observe

that the bar graph indicator for pp changes color to green and that the

Current Value Box contains no indication of alarms. Press the RESET switch

on the Rack Interface Module (RIM) to reset latching alarms.

  1. If you can not verify any configured alarm, recheck the configured setpoints.

If the monitor still does not alarm properly or fails any other part of this test,

go to Section 5.1.11 (If a Channel Fails a Verification Test).

  1. 3500/65-01-00 Disconnect the test equipment and reconnect the PWR, COM, and SIG field

wiring to the channel terminals on the I/O module. Verify that the OK LED

comes on and the OK relay energizes. Press the RESET switch on the Rack

Interface Module (RIM) to reset the OK LED.

Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!

 

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 181 0693 7731
Mail: 2872270648@qq.com
Contact: Chen