Description
GE General Electric Technical Specifications: IS200VGENH1B
The only differences in implementing the transfer scheme among the configurations presented above is by
IS200VGENH1B connecting additional logic signals to the relay when available and by placing a jumper on one logic input if the
breaker is non-drawout and has no disconnect auxiliary switches.
Besides the setpoints and logic incorporated into the IS200VGENH1B transfer scheme, the relays make use of some or all of
the logic inputs, phase instantaneous (50P-1 or 2), neutral overcurrent (50N-1 or 2), both line undervoltage ele
ments (27-3 and 27-4), and the synchrocheck (25) features of the relays.
brand | Product Name | Product model | Order No |
GE Fanuc | Module card | IS200VGENH1B | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
For the following discussion it is assumed that source 1 is the failed side. Identical logic with all 1s and 2s inter
IS200VGENH1B changed applies to relay 2 for a loss of source 2.
A transfer (trip of Incomer 1 followed by closing of the Bus Tie) from relay 1 can be initiated by:
- Operation of transformer 1 lockout relay (86T1).
- Operation of the source 1 breaker auxiliary trip device (94-1).
- Time out of relay 1 line voltage inverse time undervoltage element (27-4) caused by a low voltage on
source 1.
A transfer initiation is blocked if:
- Any of the three breakers is not in the connected state.
- Incoming breaker 2 (which is to become the new source) is presently open.
- An overcurrent condition on bus 1 is detected by 50P-1 or 2 or 50N-1 or 2, to prevent a faulted bus from
being transferred to a healthy source.
- The line voltage definite time undervoltage element (27-3) on source 2 is operated, indicating low voltage
on the other source.
IS200VGENH1B Once a condition has caused relay 1 to initiate a transfer, including the close signal to relay 3 on the Bus Tie
breaker, the command is maintained until relay 1 determines that breaker 1 has opened. When relay 3
receives the close command from relay 1, it is captured and retained until either the Bus Tie breaker closes or
the Block Transfer logic input is received. Relay 3 is inhibited from initiating a close command to breaker 3 by
its synchrocheck element. Synchrocheck is used to provide the bus decayed (residual) voltage permission-to
close, which is only provided when the bus 1 voltage decays to the preset level.
The three breakers are under prevent-parallel checking whenever the transfer scheme is operational. If a third
breaker is closed when the other two breakers are already closed, the scheme will automatically trip the
breaker selected by switch 43/10, ‘Selected To Trip’.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the de
livery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 181 0693 7731
Mail: 2872270648@qq.com
Contact: Chen