ABB 81EU01E-E GJR2391500R1210 GJR2391511R42 New PLC process control board

Numer modelu: 81EU01E-E GJR2391500R1210 GJR2391511R42
Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 5
Port isolation: 260 VDC
Weight : 3 Kg
Shipping Weight : 4 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series board
Part Number 81EU01E-E GJR2391500R1210 GJR2391511R42
Product Type board
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

The need to guarantee an ever greater continuity of service has led to an increase
in the use of emergency supply generators, either as an alternative to, or in
parallel with the public utility supply network.
Typical configurations include:
• “Island supply” (independent functioning) of the priority loads in the case of a
lack of energy supply through the public network;
• Supply to the user installation in parallel with the public supply network.
Unlike the public supply network, which has a constant contribution, in case of
a short-circuit, the current supplied by the generator is a function of the
parameters of the machine itself, and decreases with time; it is possible to
identify the following successive phases:
1. a subtransient phase: with a brief duration (10÷50 ms), characterized
by the subtransient reactance X”d (5÷20% of the rated impedance value),
and by the subtransient time constant T”d (5÷30 ms);
2. a transitory phase: may last up to some seconds (0.5÷2.5 s), and is
characterized by the transitory reactance X’d (15÷40% of the rated
impedance value), and by the transitory time constant T’d (0.03÷2.5 s);
3. a synchronous phase: may persist until the tripping of external protection,
and is characterized by the synchronous reactance Xd (80÷300% of
the rated impedance value).