Description
3500/15 133292-01 nstall the upgrade firmware ICs into the PWA.
Step 2. Install the U6 upgrade. Place part number 137494-01 into the bottom
socket on the PWA. Be sure that the notched end of the IC is matched to the
notched end of the socket. Ensure that the IC is firmly seated in the socket.
Top Shield Replacement
Replace the top shield. Be sure that the notch on the top shield is positioned at
the top left corner of the module as shown in the diagram under “Top Shield
Removal”. Align the holes in the top shield with the standoffs and press down
around each standoff until they snap in place.
This section describes how to troubleshoot a problem with the Communication
Gateway Module or the I/O module by using the information provided by the self
test, the LEDs, the System Event List, and the Alarm Event.
Self-test
To perform the Communication Gateway Module self-test:
Connect a computer running the Rack Configuration Software to the 3500 rack (if
needed).
Select Utilities from the main screen of the Rack Configuration Software.
Select System Events/Module Self-test from the Utilities menu.
Press the Module Self-test button on the System Events screen.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/15 133292-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
Select the slot that contains the Communication Gateway Module and press the
OK button. The Communication Gateway Module will perform a full self-test
and the System Events screen will be displayed. The list will not contain the
results of the self-test.
Wait 30 seconds for the module to run a full self-test.
Press the Latest Events button. The System Events screen will be updated to
include the results of the self-test.
Verify that the Communication Gateway Module passed the self-test. If the
module failed the self-test, refer to Section 7.3
Event Date: The date the event occurred.
Event Time: The time the event occurred.
Event Specific: Provides additional information for the events that use
this field.
Slot: Identifies the module that the event is associated with.
If a half-height module is installed in the upper slot or a
full-height module is installed, the field will be 0 to 15.
If a half-height module is installed in the lower slot,
then the field will be 0L to 15L. For example, a module
installed in the lower position of slot 5 would be 5L.
The following System Event List Messages are associated with the
Communication Gateway Module and are listed in numerical order. If an event
marked with a star (*) occurs, both ports on the Communication Gateway I/O
Module will stop communicating. If you are unable to solve any problems,
contact your nearest Bently Nevada office.
Flash Memory Failure
Event Number: 11
Event Classification: Potential Problem
Action: Replace the Communication Gateway Module as soon as
possible.
Internal Network Failure
Event Number: 30
Event Classification: Severe/Fatal Event
Action: Replace the Communication Gateway Module immediately.
Device Not Communicating
Event Number: 32
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
the Communication Gateway Module
the rack backplane
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact Us:+86 18106937731
Whatapp:+86 15359293870
Email: geabbdcs@gmail.com / 2872270648@qq.com
Contact Person: Chen
135785-01 3500/93 Display Unit, non backlighted
135785-02 3500/93 Display Unit, back-lighted
137412-01 3500/93 Manual
135799-01 3500/93 Display Interface Module
135799-02 3500/93 Display Interface Module
(use with A05 option only)
135813-01 3500/93 Display Interface I/O
Module
136634-0010-01 10 Foot (3 metres) Cable (PVC)
136634-0050-01 50 Foot (15 metres) Cable (PVC)
136634-0050-02 50 Foot (15 metres) Cable
(Teflon? )
136634-0100-01 100 Foot (30 metres) Cable (PVC)
136634-0100-02 100 Foot (30 metres) Cable
(Teflon? )
130121-02-01 500 Foot (152 metres) Extension
Cable (PVC)
130121-02-02 500 Foot (152 metres) Extension
Cable (Teflon? )
02200271 External Power Supply for 115 Vac
02200272 External Power Supply for 230 Vac
138227-01 Cable Adapter
146085-01 Power Cable
137224-01 System Mounting Assembly
(sheet metal for A01 & A05
options)
04309007 4-40 X 0.63 Phillips head screw for
System Mounting Assembly, 4 are
required