Description
BENTLY 128229-01 monitor provides mechanical protection
128229-01 Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O Module. Refer to Section 4.1 (Setting the I/O Jumper)for the function of
this jumper.
128229-01 Alarm Mode
Latching
Once an alarm is active, it will remain active even after the proportional value is no longer in alarm. The alarm state will continue until the channel is reset. See Page 54.
128229-01 Nonlatching
When an alarm is active, it will go inactive as soon as the proportional value is no longer in alarm. Alert is the first level alarm that occurs when the transducer signal level exceeds the selected value. Danger is the second level alarm that occurs when the transducer signal level exceeds the selected value. The Alert and Danger values are set on the Setpoint screen.
Barriers
Select the MTL 796(-) Zener External option, or Galvanic Isolators if external safety barriers are connected between the monitor and the transducer. If
using an Internal Barrier I/O Module, select the internal option. These devices are used to restrict the amount of energy that can flow into a hazardous area.
BENTLY 128229-01 monitor provides mechanical protection
128229-01 Velocity Channel Configuration Considerations
Consider the following items before configuring a Velocity Channel:
– Internal Barrier I/O Modules are not currently supported with 9200, 47633, 86205, and non-standard 2-wire seismoprobes.
– The “No Keyphasor” option is automatically selected for this channel type. No Keyphasors are required.
– The Velocity Direct full-scale range is dependent upon the transducer type.
– When a full-scale range is modified, readjust the setpoints associated with this proportional value.
– Monitors must be configured in channel pairs (for example, Channels 1 and 2 may be configured as Velocity and Channels 3 and 4 may be configured as Thrust Position).
– When integration is selected, the available Direct Full-scale Ranges will change to reflect this.
– When band-pass filtering is selected, the high-pass and low-pass filters must be set a minimum of a decade apart.
– The 100ms danger alarm is only available for the Velomitor and High Temperature Velomitor options.
The Bently 3500 online vibration monitoring system from the United States is used for mechanical protection applications, for vibration monitoring of large and medium-sized rotating machinery such as steam turbines, compressors, fans, water pumps, coal mills, gearboxes, motors, etc. It is widely used in steel, power, metallurgy, petrochemical petroleum, natural gas, petrochemical, chemical and other related industrial fields. The highly modular design of the system includes:
Bently3500/05 Instrument Frame
Bently3500/15 power supply
Bently 3500/20 Framework Interface Module
Option Description
A: Power type (upper slot)
01 Low voltage AC (85 to 132 Vac rms)
0 2 High Voltage AC (175 to 264 Vac rms)
0 3 high-voltage direct current (88 to 140 Vdc)
0 4 low-voltage DC (20 to 30Vdc)
05 Universal Power Supply
B: Power type (lower slot)
0 0 No power supply (only used when a single power supply is required)
05 Universal Power Supply
Related models:
3500/42M 140734-02
3500/42M 146449-02
3500/42M 176449-02
3500/42M-01-00
3500/42M-07-00
3500/44-01-00
3500/45
3500/45-01-00
3500/46M
3500/50
3500/50 133442-01
3500/50-01-00
3500/50-01-00-01
3500/50M
3500/53
3500/53 133388-01
3500/53-02-00
3500/53-03-00
3500/53M
3500/60
3500/60 163179-01
3500/61
3500/61-05-02
3500/62-04-00
3500/62-04-02
3500/64 140482-02
3500/65-01-00
3500/70M
3500/72M
3500/91
3500/92
3500/92 136180-01
3500/92-01-02-00
3500/92-02-01-00