Description
Specifications:
Part number: 133396-01
Manufacturer: Bently Nevada
Series: 3500
Input signal: -10 Vdc to+10 Vdc
Power consumption: 7.7 watts
Axis power supply: -24 Vdc
Product type: Transient Data Interface Module
Temperature: 25 degrees Celsius
Sensor power supply: -24 Vdc
Weight 0.45 kg
Dimensions 9.50 in x 0.96 in x 3.90 in
Supply situation: In stock
Repair: 3-7 days
Country of origin: United States
Function Description:
The Bently Nevada 133396-01 is an Overspeed Detection I/O Module designed for use in the Bently Nevada 3500 series. Here’s a summary of its key features, specifications, and frequently asked questions:
Key Features:
- Part of the Bently Nevada 3500/53 Electronic Overspeed Detection System.
- Highly dependable and quick-response redundant tachometer system.
- Designed for use as part of an Overspeed safety system, meeting API Standards 670 and 612.
- Can be combined with other modules to form a 2-out-of-2 or 2-out-of-3 voting system.
- Requires a 3500 rack with multiple power sources.
Inputs Signal Specifications:
- Accepts a single transducer signal from a proximity probe transducer or magnetic pickup.
- Input signal voltage range: +10.0 V to -24.0 V.
- Internally limits signals that exceed this range.
Front Panel LEDs:
- OK LED: Indicates the module is in good working order.
- TX/XR LED: Indicates communication with other modules in the 3500 rack.
- Bypass LED: Illuminates when the module is in Bypass Mode.
- Test Mode LED: Indicates when the module is in Test Mode.
- Alarm LEDs: Indicate alarm conditions with associated relays.
Transducer Conditioning:
- Auto Threshold: Minimum triggering signal amplitude is 1 volt peak-to-peak.
- Manual Threshold: User-selectable from +9.9 Vdc to -23.9 Vdc. Minimum triggering signal amplitude is 500 millivolts peak-to-peak.
- Hysteresis: User-configurable, ranging from 0.2 to 2.5 volts.
Alarm Setpoints:
- Speed can be set to Under and Over Alert levels (setpoints).
- Danger (Overspeed) setpoint can be set for speed.
- Configurable using software, with customizable alarms.
Frequency Response Speed Input:
- Maximum full-scale range: 99,999 rpm.
- Maximum input frequency: 20 kHz.
- Supports 1 to 255 events per revolution.
- Minimum input frequency for proximity transducers: 0.0167 Hz.
- Minimum input frequency for passive magnetic pickups: 3.3 Hz.
Product Attributes:
- Power Consumption: 8.0 watts, typical.
- Transducer Power Supply: -24 Vdc, 40 mA maximum.
- Environmental Sealing: Epoxy sealed.
- Recorder Output: +4 to +20 mA, proportional to the full-scale range.
- Weight: 0.45 kg.
Environmental Limits:
- Operating Temperature: -30 °C to +65 °C.
- Storage Temperature: -40 °C to +85 °C.
- Humidity: 95%, non-condensing.
Frequently Asked Questions:
- What is Bently Nevada 133396-01?
- It is an Overspeed Detection I/O Module developed by Bently Nevada under the 3500 series.
- What is the Operating Temperature of the component?
- The operating temperature ranges from -30 degrees Celsius to +65 degrees Celsius.
- What is the Storage Temperature of the component?
- The storage temperature ranges from -40 degrees Celsius to +85 degrees Celsius.
- How much does the component weigh?
- The component weighs around 0.45 kg.
- How much is the typical power consumption of the component?
- The typical power consumption is 8.0 watts.
- How to obtain 133396-01?
- Contact WOC of Bently Nevada spare parts. They supply worldwide.
Spare parts:
3500/04 136719-01 I.S. Earthing I/O Module
3500/05
138945-01 Standard Backplane
144464-01 Mini-Rack Backplane
138953-01 Bulkhead Backplane
143728-01 Bulkhead Backplane MOD
3500/15
129486-01 High Voltage DC Power Supply Module
133292-01 Low Voltage DC Power Supply Module
133300-01 Low Voltage DC Power Input Module (LVDC PIM)
129478-01 High Voltage DC Power Input Module (HVDC PIM)
106M1079-01 Universal AC Power Supply Module
106M1081-01 Universal AC Power Input Module (AC PIM)
114M5329-01 REFRESH HVDC POWER SUPPLY MODULE
114M5330-01 REFRESH LVDC power supply module
114M5335-01 REFRESH LVDC PIM
115M7750-01 REFRESH HVDC PIM
3500/22
288055-01 Standard Transient Data Interface Monitor Module with USB cable (non-TMR)
288055-02 TMR Transient Data Interface Module with USB cable
146031-01 10Base-T/100Base-TX I/O Module
146031-02 100Base-FX (Fiber Optic) I/O Module
146031-03 10Base-T/100Base-TX I/O Module (GLD RLY)
146031-04 100Base-FX (Fiber Optic) I/O Module (GLD RLY)
147364-01** Buffered Signal Output Module
3500/25
149369-01 Enhanced Keyphasor Monitor Module
125800-01 Keyphasor I/O Module (Internal Terminations)
125800-02 Isolated Keyphasor I/O Module (Internal Terminations)
126648-01 Keyphasor I/O Module (External Terminations)
126648-02 Isolated Keyphasor I/O Module (External Terminations)
135473-01 Keyphasor I/O Module (Internal Barriers and Internal Terminations)