Description
BENTLY 149986-01 monitor provides mechanical protection
149986-01 Zero Position (Direct)
149986-01 Represents the transducer DC voltage corresponding to the zero indication on the channel’s meter scale for the direct proportional value. The amount of adjustment allowed is dependent upon the 149986-01 Direct Full Scale Range and the transducer OK limits. For maximum amount of zero adjustment, gap the transducer as close as possible to the ideal zero position voltage based on the full-scale range, the transducer scale factor, and the Upscale Direction. For a mid-scale zero the ideal gap is the center of the range.
149986-01 Adjust Button
Adjust the Zero Position voltage. When this button is clicked a utility starts that helps you set the direct zero position voltage. Since this utility provides active feedback from the 3500 rack, a connection with the rack is required. Refer to Section 5.2 (Adjusting the Scale Factor and the Zero Position).
BENTLY 149986-01 monitor provides mechanical protection
149986-01 Alarm Mode
Latching
Once an alarm is active it will remain active even after the proportional value drops below the configured setpoint level. The channel will remain in alarm until it is reset using one of the following methods:
– the reset switch on the front of the Rack Interface Module
– the contact on the Rack Interface I/O Module
– the Reset button in the Operator Display Software
– the reset command through the Communication Gateway Module
– the reset command through the Display Interface Module
– the reset command in the Rack Configuration Software
149986-01 Nonlatching
When an alarm is active it will go inactive as soon as the proportional value drops below the configured setpoint level. Alert should be the first level alarm that occurs when the transducer signal level exceeds the selected value. Danger should be the second level alarm that occurs when the transducer signal level exceeds the selected value. The Alert and Danger values are set on the Setpoint screen.
The Bently 3500 online vibration monitoring system from the United States is used for mechanical protection applications, for vibration monitoring of large and medium-sized rotating machinery such as steam turbines, compressors, fans, water pumps, coal mills, gearboxes, motors, etc. It is widely used in steel, power, metallurgy, petrochemical petroleum, natural gas, petrochemical, chemical and other related industrial fields. The highly modular design of the system includes:
Bently3500/05 Instrument Frame
Bently3500/15 power supply
Bently 3500/20 Framework Interface Module
Option Description
A: Power type (upper slot)
01 Low voltage AC (85 to 132 Vac rms)
0 2 High Voltage AC (175 to 264 Vac rms)
0 3 high-voltage direct current (88 to 140 Vdc)
0 4 low-voltage DC (20 to 30Vdc)
05 Universal Power Supply
B: Power type (lower slot)
0 0 No power supply (only used when a single power supply is required)
05 Universal Power Supply
Related models:
3500/42M 140734-02
3500/42M 146449-02
3500/42M 176449-02
3500/42M-01-00
3500/42M-07-00
3500/44-01-00
3500/45
3500/45-01-00
3500/46M
3500/50
3500/50 133442-01
3500/50-01-00
3500/50-01-00-01
3500/50M
3500/53
3500/53 133388-01
3500/53-02-00
3500/53-03-00
3500/53M
3500/60
3500/60 163179-01
3500/61
3500/61-05-02
3500/62-04-00
3500/62-04-02
3500/64 140482-02
3500/65-01-00
3500/70M
3500/72M
3500/91
3500/92
3500/92 136180-01
3500/92-01-02-00
3500/92-02-01-00