Description

Pass Main Board +15V-AB (Pass Main Board +15V – upper and lower Power

Supplies)

Event Number: 111

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

The Monitor Module

The Power Supply installed in the supper slot

The Power Supply installed in the lower slot

Fail Main Board -24V-A (Fail Main Board -24V – upper Power Supply)

Event Number: 112

Event Classification: Potential Problem

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the upper slot

Pass Main Board -24V-A (Pass Main Board -24V – upper Power Supply)

Event Number: 113

Event Classification: Potential Problem

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the upper slot

Fail Main Board -24V-B (Fail Main Board -24V – lower Power Supply)

Event Number: 114

Event Classification: Potential Problem

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the lower slot

Pass Main Board –24V-B (Fail Main Board –24V – lower Power Supply)

Event Number: 115

Event Classification: Potential Problem

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the lower slot

brand Product Name Product model Order No
BENTLY modular 161204-01 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1810693-7731

 

Fail Main Board -24V-AB (Fail Main Board -24V – upper and lower Power

Supplies)

Event Number: 116

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the upper slot

the Power Supply installed in the lower slot

Monitor Module will stop alarming.

Pass Main Board -24V-AB (Pass Main Board -24V – upper and lower Power

Supplies)

Event Number: 117

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the upper slot

the Power Supply installed in the lower slot

* Fail Main Board +5VA-AB (Fail Main Board Analog +5V – upper and lower

Power Supplies)

Event Number: 126

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the problem. If

the problem is not caused by noise, check to see if one of the

following components is faulty:

the Monitor Module

the Power Supply installed in the upper slot

the Power Supply installed in the lower slot

Monitor Module will stop alarming.

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact Us:+86 18106937731
Whatapp:+86 15359293870
Email: geabbdcs@gmail.com / 2872270648@qq.com
Contact Person: Chen

 

135785-01 3500/93 Display Unit, non backlighted
135785-02 3500/93 Display Unit, back-lighted
137412-01 3500/93 Manual
135799-01 3500/93 Display Interface Module
135799-02 3500/93 Display Interface Module
(use with A05 option only)
135813-01 3500/93 Display Interface I/O
Module
136634-0010-01 10 Foot (3 metres) Cable (PVC)
136634-0050-01 50 Foot (15 metres) Cable (PVC)
136634-0050-02 50 Foot (15 metres) Cable
(Teflon? )
136634-0100-01 100 Foot (30 metres) Cable (PVC)
136634-0100-02 100 Foot (30 metres) Cable
(Teflon? )
130121-02-01 500 Foot (152 metres) Extension
Cable (PVC)
130121-02-02 500 Foot (152 metres) Extension
Cable (Teflon? )
02200271 External Power Supply for 115 Vac
02200272 External Power Supply for 230 Vac
138227-01 Cable Adapter
146085-01 Power Cable
137224-01 System Mounting Assembly
(sheet metal for A01 & A05
options)