Description
Main features of 6105-WA-PDPS
Low nonlinearity: Typical: 0.1% Best: 0.01%
Low temperature coefficient: -65ppm/℃
Wide? Frequency? Band: High precision: DC-10kHz
High speed achievable: 5MHz
Main technical indicators of 6105-WA-PDPS
Executive standard: QB/441600 17 079-2001
Accuracy: 0.2%, 0.5%
Overall power consumption: ≤ 1.0VA
Work stability: annual change<0.2%
Power frequency withstand voltage: AC2.0kV/min.1mA
Insulation resistance: ≥ 20M Ω (DC500V)
Impulse voltage: 5kV (peak), 1.2/50 μ S
Response time: ≤ 350ms
Input range: DC0~5A, DC0~500V optional
Absorbed power: < 0.1VA Overload capacity: Current: 1.5 times continuous, 20 times per second. Voltage: 2 times continuous
Output signals: DC0-5V, 1-5V, 0-20mA, 4-20mA, 1-3-5V, 4-20mA, etc
Load resistance: Current output: RL ≤ 270 Ω at+12V,+15V auxiliary power supply
+RL ≤ 600 Ω for 24V auxiliary power supply
Voltage output: RL ≥ 2K Ω
Working environment: -10~50 ℃, 20%~90% non condensing
Storage environment: -40~70 ℃, 20%~95% without condensation
Installation method: DIN (35mm) guide rail and M3 screw fixation
Boundary dimension: 42mm × 75 mm × 70mm
The module provides information on diagnostics and troubleshooting in the following forms:
· LED status indicators on the front of the module provide general information on the module’s status.
· You can view status data contained in the module through the Ethernet port, using the troubleshooting and diagnostic capabilities of ProSoft Configuration Builder (PCB).
· You can transfer status data values from the module to processor memory and can monitor them in the processor manually or by customer-created logic.
Typically, if the OK LED on the front of the module remains RED for more than ten seconds, a hardware problem has been detected in the module or the program has exited. To clear the condition, follow these steps:
1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed correctly.
5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the CompactLogix controller. If the module’s OK LED does not turn GREEN, verify that the module is inserted completely into the rack. If this does not cure the problem, contact ProSoft Technology Technical Support.