CI540 3BSE001077R1 ABB analog expansion module out of production spare parts

Product name:CI540 3BSE001077R1 ABB analog expansion module out of production spare parts
Product model:CI540 3BSE001077R1
Quantity: stock on hand
Price: electricity
Product documentation: No relevant documentation

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

SW1 Reserved
SW2 Reserved
SW3 SW4 Operation Mode
ON ON Runs user application
ON OFF Runs burn-in test program
OFF ON Updates BIOS
OFF OFF Runs bench test program
SW5 Communication Parameters
ON The operator terminal uses the communication parameters
defined on the operator terminal’s configuration screen for
controller communication.


OFF The operator terminal uses the communication parameters
defined in CP400Soft for controller communication.
SW6 Password
ON The operator terminal asks the operator to enter a password
after power-on self-test.
OFF No password is required to start the operator terminal.
SW7 System Menu
ON The operator terminal displays the system menu.
OFF The operator terminal runs user application without displaying
the system menu.
SW8 Default User Level
ON The default user level is set to 1 if the operator terminal
requires no password to start its operation.
OFF The default user level is set to 9 if the operator terminal
requires no password to start its operation.
SW9 Reserved
SW10 COM2 Port
ON For RS485, this switch has to be set ON.
OFF For RS422, this switch has to be set OFF.
SW11 COM3 Port
ON For RS485, this switch has to be set ON.
OFF For RS422, this switch has to be set OFF.
SW12 Reserved

COM1, a 9-pin female connector, is used to connect the operator terminal to a
controller via RS232 or RS485.
COM2, a 25-pin female connector, is used to connect the operator terminal to
a controller via RS232, RS422 or RS485.
COM3, a 9-pin female connector, is used to connect the operator terminal to a
controller via RS422 or RS485.
Note:
Make sure that the connection is in accordance with the setting of the dip switches,
for example RS485 corresponds to SW10 = ON and SW11 = ON.
See section 4 Dip Switches.

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com