ABB CP435T 1SBP260193R1001 Analog module industrial system controller

Numer modelu: CP435T 1SBP260193R1001
Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 4
Port isolation: 220 VDC
Weight : 1 Kg
Shipping Weight : 2 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number CP435T 1SBP260193R1001
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

The PM891 processor unit is a monolithic unit equipped with power supply and
CPU-boards, and unit termination.
The unit contains the microprocessor and RAM memory, a real-time clock, LED
indicators, INIT push button, and a Secure Digital interface.
The PM891 does not contain any internal battery.
The main function of the power supply board is to generate isolated, short circuit
proof +5 V and +3.3 V supplies, for the CPU and I/O units. The board also contains
opto-isolated RS-232C drivers / receivers for the service port.
The PM891 processor unit is grounded to the DIN rail by means of the metallic
components of the housing. The unit consists of screw terminals for power supply
(L+, L-); redundant power supply monitoring (supervision signals SA, SB); RJ45
connectors for the control network and service port; connectors for the optical
ModuleBus and the CEX-Bus. All units on the CEX-Bus are powered by the 24 V
d.c. connected to the unit. The CN1 and CN2 ports are used for connection of
Control Network. CN1 should be used in a single network. Both ports should be
used for a redundant network.
In single CPU configuration, it is possible to connect an S800 I/O cluster directly to
the built-in optical ModuleBus plug located at the lower side of the unit.