- DSQC668 Use of Standard CT Ratios
- Standard CT ratios: CT2 / CT1=V1 / V2
- Tapped relay windings / interposing CTs (inaccurate/expensive)
Solution:
- Wx Nom Voltage, Wx rated Load, DSQC668 Wx CT primary setpoints
- Automatic correction for mismatch: (CT2 × V2) / (CT1 × V1) < 16
Even ignoring the onload tap changer, the 1500/1 CT on winding 2 does not perfectly
match the 500/1 CT on winding 1. A perfectly matched winding 2 CT ratio (at nominal
-
winding 2 voltage) is calculated as follows:
(EQ 5.1)
CT2 (ideal) CT
1
V
1
V2
× —–
500
1
———
220 kV
69 kV
—————-
–
×
1594.2
where CT1 = winding 1 CT ratio
V1 = winding 1 nominal voltage
CT2 = winding 2 CT ratio
V2 = winding 2 nominal voltage
Thus, for any load, the winding 2 CT secondary DSQC668 current is higher (per unit) than the
winding 1 CT secondary current. The mismatch factor is 1594.2 / 1500 = 1.063.
The transformer type is entered as S2 SYSTEM SETUP TRANSFORMER TRANSFORMER
TYPE. The 745 calculates and automatically corrects for CT mismatch to a maximum
mismatch factor of 16. The following information is entered as setpoints:
S2 SYSTEM SETUP WINDING 1 WINDING 1 NOM F-F VOLTAGE: “220 kV”
S2 SYSTEM SETUP WINDING 1 WINDING 1 RATED LOAD: “100 MVA”
S2 SYSTEM SETUP WINDING 1 WINDING 1 PHASE CT PRIMARY: “500:1 A”
S2 SYSTEM SETUP WINDING 2 WINDING 2 NOM F-F VOLTAGE: “69.0 kV”
S2 SYSTEM SETUP WINDING 2 WINDING 2 RATED LOAD: “100 MVA”
S2 SYSTEM SETUP WINDING 2 WINDING 2 PHASE CT PRIMARY: “1500:1 A”
For a three-winding transformer, DSQC668 the setpoints under the S2 SYSTEM SETUP WINDING 3
menu must also be set.
5.2.2.2 Onload Tap Changer
- Onload tap changer
- Variable voltage ratio
- CT2 / CT1 = V1 / V2
- Lower sensitivity on differential element
Solution:
- Tap position monitoring: V2 = Vmin + (n – 1)Vincr
For example, the onload tap changer changes the winding 2 voltage, resulting in an even
greater CT mismatch. A perfectly matched winding 2 CT ratio (based on the tap changer
position) is calculated as follows:
(EQ 5.2)
where
n = current tap changer position
V2(min) = winding 2 minimum voltage (at n = 1)
V2(tap) = winding 2 voltage increment per tap
Thus, with the tap changer at position 33, the Winding 2 CT ratio must be 1428.6 / 1 to be
DSQC668 perfectly matched. In this case, the mismatch factor is 1428.6 / 1500 = 0.952.
The 745 allows monitoring of the tap changer position via the tap position input. With this
input, the 745 dynamically adjusts the CT ratio mismatch factor based on the actual
transformer voltage ratio set by the tap changer.
Tap changers are operated by means of a motor drive unit mounted on the outside of the
transformer tank. The motor drive is placed in a protective housing containing all devices
necessary for operation, including a tap position indication circuit. This indication circuit
has a terminal for each tap with a fixed resistive increment per tap. A cam from the drive
shaft that provides local tap position indication also controls a wiper DSQC668 terminal in the
indication circuit, as illustrated below.