- DSTC456 This section contains the settings to configure the tap position input. The 745 accepts a
resistive input from the tap changer control circuitry, which is used in the 745 to
dynamically correct for CT ratio mismatch based on the dynamically changing voltage
ratio of the transformer. Thus, the percent differential DSTC456 function of the device can be set for
greater sensitivity. See Dynamic CT Ratio Mismatch Correction on page 5–6 for more details
on the tap position input.
-
WINDING WITH TAP CHANGER: Enter the winding with the tap changer. Enter ‘None’
for a transformer with no onload tap changer, or to disable this feature.
NUMBER OF TAP POSITIONS: Enter the number of tap positions here.
MINIMUM TAP POSITION VOLTAGE: Enter the DSTC456 voltage at the lowest tap position. This is
an auto-ranging setpoint dependent on S2 SYSTEM SETUP TRANSFORMER LOW
VOLTAGE WINDING RATING; see ranges in the table below.
VOLTAGE INCREMENT PER TAP: Enter the voltage increment for each tap. The range is
affected by the setpoint. This is an auto-ranging setpoint dependent on the S2 SYSTEM
SETUP TRANSFORMER LOW VOLTAGE WINDING RATING value; see ranges in the
following table:
- The 745 calculates the individual harmonics in each of the phase current inputs up to the
21st harmonic. With this information, it calculates an estimate of the effect of non
sinusoidal load currents on the transformer rated full load current. These calculations are
based on ANSI/IEEE Standard C57.110-1986, and DSTC456 require information that is often only
available from the transformer manufacturer’s test report, including the three-phase
resistance of each winding and the load loss at rated load. The harmonic derating factor
will only be valid if this information has been entered correctly.
The 745 also calculates the total harmonic distortion of the phase current input signals.
The band of frequencies over which this calculation is made can be changed to be more
selective than the default 2nd to 21st harmonics.
HARMONIC DERATING FUNCTION: Enter “Enabled” to enable the harmonic derating
factor calculations.
THD MINIMUM/MAXIMUM HARMONIC NUMBER Enter the minimum/maximum
harmonic number of the frequency band over which total harmonic distortion is
calculated.