PFSA145 The THD elements will only operate if the amplitude of the fundamental component is
above the threshold setting.
To verify this threshold,
Initially set the fundamental component above the threshold, with a
harmonic content high enough to PFSA145 cause the element to operate.
Now reduce the fundamental component only.
This will have the effect of increasing the THD level. When the
fundamental component reaches a value below the set threshold, the
element will reset.
If an RMS-responding meter is used to measure the current signal, the reading is the
total value of current. To determine the fundamental component only, use the relay
values in A2 METERING CURRENT W1 CURRENT. These values represent the
fundamental component only.
7.6.1.4 Other THD Elements
A THD element can be programmed for PFSA145 each winding of the transformer. Use the above
procedures to verify the element(s) on the other winding(s).
7.6.2 Harmonic Derating Function
Testing of the harmonic derating function requires that accurate transformer parameters
such as load losses at rated load and winding resistance be entered. This feature makes
use of the harmonic derating factor (HDF) computed by the relay, using the harmonic
content of the current signals and the transformer data (refer to IEEE C57.110-1986 for the
computation method). Once the derating PFSA145 factor falls below a set value, the 745 can trip
and/or alarm.
7.6.2.1 Operating level
To verify the correct operation of this element, a current signal containing harmonics must
be introduced into one phase of the relay. Use FIGURE 7–1: Test setup on page 7–4 to
accomplish this.
Set the fundamental component at rated CT secondary into winding 1
phase A.
Gradually increase the second harmonic component (and the rest of the
even harmonics) while displaying PFSA145 the A2 METERING HARMONIC
CONTENT HARMONIC DERATING W1(3) HARMONIC
DERATING FACTOR value.
The element should operate when the displayed HDF equals the element
setting.
Check that the Trip, Pickup (and Alarm if selected) LEDs are on, and
one of the following is displayed:
LATCHED: W1 Harm Derating or OPERATED: W1 Harm
Derating
Lower the DC component until the element resets.
The reset value should be approximately 2% larger than the operate
value.
Verify that the Pickup and Alarm LEDs reset if the target function is set
to Self-resetting.
The Trip LED should remain latched.
7.6.2.2 Operating Time
To measure the basic operating time of this element,
Preset a fundamental and DC component composite current signal to
cause the element to operate.
Using the setup of FIGURE 7–1: Test setup on page 7–4, apply the
current suddenly, at the same time the timer is triggered.
The measured operating time should correspond to the time delay
setting for the element.
7.6.3 Transformer Overload
The transformer overload element uses the phase A current of each winding to compute a
transformer loading. The computation assumes a rated voltage on the wInding, hence the
loading is effectively a percent of rated load current.
7.6.3.1 Operating Level
Inject a fundamental-frequency current into phase a of winding 1.
Increase the current signal to a value just above the transformer
overload pickup setting (take into account the CT ratio and the rated
MVA phase current to set the current correctly).
The element should operate after its set time delay.
Check that the Trip, Pickup (and Alarm if selected) LEDs are on, and
one of the following is displayed:
LATCHED: Xformer Overload or OPERATED: Xformer Overload
Lower the current until the element resets.
The reset value should be approximately 97% of the operate value.
Verify that the Pickup and Alarm LEDs reset if the target function is set
to Self-resetting.
The Trip LED should remain latched.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen