Description
PP220 3BSC690099R1 The Safety Digital Input (SDI) board used with Safeguard 400 Series is DSDI 110N.This is
based on the DSDI 110A for the normal S100 I/O system. The connection units are made with
dual connections. The DSDI 110N board is used with connection unit DSTD N030 with one or
two logic boards DSTD N031.
The DI-board database configuration is equal PP220 3BSC690099R1 to DSDI 110. Channel 32 is used as the test
indication signal between the connection unit and the input board.
The loop signals are connected to the connection unit. This unit contains:
- Terminals for connection of 31 field input signals. PP220 3BSC690099R1 Power distribution for the field
devices.ï
- The field termination unit is equipped with logic boards for generation of test patterns. It
can be configured with one or two logic boards. One logic board is used in single
controller systems. With two logic boards, each board is generating independent test
signals for each controller in a dual system. A yellow LED indicates that the test is
running.
The input board DSDI 110N contains:
In addition to the verification PP220 3BSC690099R1 of the test patterns from the connection unit, the digital input
board performs several internal diagnostics.
3.2.2 Output Subsystem
The local output subsystem consists of S100 I/O output cards mounted in the S100 I/O sub-rack.
Local outputs are available in the following types:
- Master Vote 3000 safety digital outputs (24 VDC)
- Normally Energized (NE) outputs for e.g. shutdown valves
- Normally De-energized (ND) outputs for e.g. fire protection devices
- DSDO 110 non fail-safe digital outputs, transistor type, for status outputs. (relay output)
- DSDO 115 non fail-safe digital outputs, relay type, for status outputs. (24 VDC)
- DSAX 110 analog I/O for PID control in high availability control systems
- DSAO 130 analog output signals.
3.2.2.1 Master Vote 3000, safety digital outputs
The Master Vote 3000 output stage is a safety output unit designed to reduce output spurious
trips to a minimum, while at the same time guaranteeing executive action on demand. The
Master Vote 3000 units are designed to PP220 3BSC690099R1 support extended and independent self-testing and
monitoring functions, including associated field devices such as cables and actuators. The
system incorporates a fail-to-safe isolate function, and offers true output state read-back and
continuous loop fault monitoring.
The Master Vote 3000 functions handle:
- One out of two output voting (1oo2D) in normal operation for Normally Energized (NE)
and Normally De-energized (ND) signals.
- Performs active testing and diagnosis on itself and the processing units to control fault
tolerant and fail-to-safe fall-back.
- Permits isolation of one branch for maintenance operations.
- Tests and/or read-back the field output loops to provide information on internal and
external component malfunctions.
Normally Energized (NE) outputs power the field device during normal operation. Power is
interrupted to cause shutdown action. These outputs are used for shutdown valves, fire dampers
and similar devices where fail-to-safe action is required. The fail-to-safe action is to de
energize.
Normally De-energized (ND) outputs control field devices that are not powered during normal
operation. Power is applied to cause action. These outputs are used for fire fighting, and
alarming devices that do not require action on failure to take place. The fail-to-safe action is to
remain de-energized.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen