Description
Manufacturer | ABB |
Brand | ABB |
Series | module |
Part Number | SA9923A-E |
Product Type | module |
Quality | 100% New Original |
Stock | In stock |
Delivery time | 1-3 days after Payment |
After-sales Service | Have |
Warranty | 1 year |
Shipping term | DHL / FEDEX/ EMS /UPS/TNT/EMS |
Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.
Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Information on trip and opening data
If a trip occurs, Ekip Touch stores all the information that is required for rapid
identification and elimination of the causes:
– Protection tripped
– Opening data (current, voltage or frequency)
– Time-stamping (data, time and consecutive opening number)
If the iTest key is pressed, the trip unit displays all these data directly on the display.
No auxiliary supply is required. The information is also available to the user with the
circuit-breaker open or without current flow, due to the battery installed inside the unit.
Maintenance indicators
A complete set of information about the circuit-breaker and its operation is available
for effective fault analysis and preventive scheduling of maintenance. All the
information can be seen from the display or from a PC using a communication unit.
In particular:
– Date, time, fault current by phase and type of protection tripped over the last 30
trips;
– Date, time and type of operation of the last 200 events (example: opening/closing
of circuit-breaker, pre-alarms, editing of settings, ect.);
– Number of operations of the circuit-breaker: divided into mechanical operations
(no current), electrical operations (with current) and protection function (trip);
– Contact wear estimated in function of the number and type of openings;
– Total operating time of the circuit-breaker with circulating current;
– Date and time of the last maintenance session, scheduling of the next
maintenance session;
– Circuit-breaker identifying data: type, serial number, firmware version, device
name assigned by the user.
All the information can be viewed directly from the display and from a Smartphone,
Tablet (with Ekip Bluetooth) or PC using the front port of the trip unit or the system
communication.