ABB SB510 3BSE000860R1 After sales service is provided for the control card of the power supply device

Numer modelu: SB510 3BSE000860R1

Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 9
Port isolation: 120 VDC
Weight :3Kg
Shipping Weight :5 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number SB510 3BSE000860R1
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

Protection functions
The Ekip Hi-Touch trip unit has the following protection functions, which it shares with Ekip Touch:
– Overload (L – ANSI 49);
– Time-delayed overcurrent (S – ANSI 51 & 50TD);
– Thermal memory;
– Instantaneous overcurrent (I – ANSI 50);
– Closing on short-circuit (MCR);
– Earth fault (G – ANSI 51N & 50NTD);
– Earth fault on toroid (G ext – ANSI 51G & 50GTD)
– Neutral protection;
– Start-up function;
– Zone selectivity for functions S and G (ANSI 68);
– Current unbalance (IU – ANSI 46);
– Undervoltage (UV – ANSI 27);
– Overvoltage (OV – ANSI 59);
– Underfrequency (UF – ANSI 81L);
– Overfrequency (OF – ANSI 81H);
– Voltage unbalance (VU – ANSI 47);
– Residual current (Rc – ANSI 64 & 50NTD);
– Reverse active power (RP – ANSI 32R);
– Synchrocheck (SC – ANSI 25, optional);
– Cyclical direction of the phases (ANSI 47);
– Power factor (ANSI 78);
– Current thresholds;
– Power Controller function (optional).
The following protections are also available:
Second time-delayed overcurrent protection (S2 – ANSI 50TD): in addition to the standard protection
S, a second (excludible) time-constant protection is available that enables two independent thresholds to
be set in order to ensure precise selectivity, especially in highly critical conditions.
Second protection against earth fault (ANSI 50GTD/51G & 64REF): whereas with Ekip Touch the
user has to choose between implementation of the protection G by internal current sensors (calculating
the vector sum of the currents) or G ext external toroids (direct measurement of the earth fault current),
Ekip Hi-Touch offers the exclusive feature of simultaneous management of both configurations by two
independent earth fault protection curves. Owing to this characteristic, the trip unit is able to distinguish
a non-restricted earth fault and then activate the opening of Emax 2, from a restricted earth fault, and to
thus command the opening of the medium voltage circuit-breaker.
Another possible configuration is with the residual current protection replacing the Gext protection, whilst the
G protection remains active. The residual current protection is activated in the presence of the residual current
rating-plug and of the toroid.