ABB TC520 3BSE001449R1 After sales service is provided for the control card of the power supply device

Numer modelu: TC520 3BSE001449R1

Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 9
Port isolation: 120 VDC
Weight :3Kg
Shipping Weight :5 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number TC520 3BSE001449R1
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

The neutral conductor is a conductor that is connected to the system neutral
point (which generally but not necessarily coincides with the star centre of the
secondary windings of the transformer or the windings of the generator); it is
able to contribute to the transmission of electric power, thereby making available
a voltage that is different from the phase to phase voltage. In certain cases and
under specific conditions, the functions of neutral conductor and protective
conductor can be combined in a single conductor (PEN).
Protection and disconnection of the neutral conductor
If fault conditions arise, a voltage to earth may occur on the neutral conductor.
This may be caused by a phase to neutral short-circuit and by the disconnection
of the neutral conductor due to accidental breaking or to tripping of single-pole
devices (fuses or single-pole circuit breakers).
If the neutral conductor only is disconnected in a four-conductor circuit, the
supply voltage to the single-phase loads may be altered so that they are supplied
by a voltage different from the U0
phase to neutral voltage (as shown in Fig. 1).
Therefore, all the necessary measures to prevent this type of fault shall be taken,
e.g. by not protecting the neutral conductor with single-pole devices.
1.5 Neutral and protective conductors
Figure 1: Disconnection of the neutral conductor
Moreover, in TN-C systems, voltage to earth arising on the neutral conductor
constitutes a hazard for people; in fact, since this conductor is also a protective
conductor, this voltage reaches the connected exposed conductive parts. For
TN-C systems, the Standards specify minimum cross sections (see next clause)
for the neutral conductor in order to prevent accidental breaking and they
forbid the use of any device (single-pole or multi-pole) that could disconnect
the PEN