ABB UAC317AEV1 After sales service is provided for the control card of the power supply device

Numer modelu: UAC317AEV1

Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 9
Port isolation: 120 VDC
Weight :3Kg
Shipping Weight :5 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number UAC317AEV1
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

The full voltage three-phase short-circuit current (Ik
), at the LV terminals of the
transformer, can be expressed as (assuming that the short-circuit power of
the network is infinite):
where:
uk
% is the short-circuit voltage of the transformer, in %.
The protection circuit-breaker must have: (*)
I
n ≥ Ir
;
I
cu (Ics) ≥ Ik
.
If the short-circuit power of the upstream network is not infinite and cable or
busbar connections are present, it is possible to obtain a more precise value for
I
k
by using formula (1), where ZNet is the sum of the impedance of the network
and of the impedance of the connection.
MV/LV substation with more than one transformer in parallel
For the calculation of the rated current of the transformer, the above applies
(formula 4).
The breaking capacity of each protection circuit-breaker on the LV side shall
be higher than the short-circuit current equivalent to the short-circuit current of
each equal transformer multiplied by the number of them minus one.
As can be seen from the diagram below, in the case of a fault downstream of a
transformer circuit-breaker (circuit-breaker A), the short-circuit current that flows
through the circuit-breaker is equal to the contribution of a single transformer.
In the case of a fault upstream of the same circuit-breaker, the short-circuit
current that flows is equal to the contribution of the other two transformers
in parallel.

The tables refer to the previously specified conditions; the information for the
selection of circuit-breakers is supplied only with regard to the current in use and
the prospective short-circuit current. For a correct selection, other factors such
as selectivity, back-up protection, the decision to use limiting circuit- breakers
etc. must also be considered. Therefore, it is essential that the design engineers
carry out precise checks.
It must also be noted that the short-circuit currents given are determined using
the hypothesis of 750 MVA power upstream of the transformers, disregarding
the impedances of the busbars or the connections to the circuit-breakers.
Example:
Supposing the need to size breakers A1/A2/A3, on the LV side of the three
transformers of 630 kVA 20/0.4 kV with uk
% equal to 4% and outgoing feeder
circuit-breakers B1/B2/B3 of 63-400-800 A: