Description
3500/01-01 Represents the transducer DC voltage corresponding to the zero indication on the
channel’s meter scale for the direct proportional value. The amount of
adjustment allowed is dependent upon 3500/01-01 the Direct Full Scale Range and the
transducer OK limits. To ensure maximum amount of zero adjustment, gap the
probe as close as possible to the center gap voltage specified in the OK Limit
table.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/01-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1806092-3929 |
3500/01-01 Adjust the Zero Position voltage. When this button is clicked a utility starts that
helps you set the direct zero position voltage. Since this utility provides active
feedback from the 3500 rack, a connection with the rack is required. Refer to
Section 5.2 (Adjusting the Scale Factor and the Zero Position).
Transducer
3500/01-01 The following transducer types are available for the Eccentricity Channel (non
barrier I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
3300 – 16 mm HTPS
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
7200 – 11 mm Proximitor
The following transducer types are available for the Eccentricity Channel (barrier
I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
Nonstandard
Customize button
3500/01-01 Used to adjust the Scale Factor for transducers. If Non-standard is selected as
the transducer type, the OK Limits can also be adjusted. The Non-standard
transducer’s scale factor must be between 85 and 230 mV/mil. Also, there must
be at least 2 volts between the Upper and Lower OK Limits.
Latching
Once an alarm is active, it will remain active even after the proportional value
drops below the configured setpoint level. 3500/01-01 The channel will remain in alarm
until it is reset using one of the following methods:
– the reset switch on the front of the Rack Interface Module
– the contact on the Rack Interface I/O Module
– the Reset button in the Operator Display Software
– the reset command through the Communication Gateway Module
– the reset command through the Display Interface Module
– the reset command in the Rack Configuration Software
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen