3500/15-02-00-00 The following sections describe how to test alarms, verify channels, and test OK

limits for channels configured as Thrust Position and Differential Expansion. The

output values and alarm setpoints are verified by 3500/15-02-00-00 varying the input DC voltage

from a power supply and observing that the correct results are reported in the

Verification screen on the test computer.

 

brand Product Name Product model Order No
BENTLY modular 3500/15-02-00-00 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1806092-3929

 

3500/15-02-00-00 Run the Rack Configuration Software on the test computer. Choose Verification

from the Utilities menu and choose the proper Slot number and Channel number

then click on the Verify button.

The following table directs you to the starting page of each maintenance section

associated with the Thrust Position and Differential Expansion Channels.

3500/15-02-00-00 The general approach for testing alarm setpoints is to simulate the Thrust Position

and Differential Expansion signal with a power supply. The alarm levels are

tested by varying the DC voltage and observing that the correct results are

reported in the Verification screen on the test computer. It is only necessary to

test those alarm parameters that are configured and being used. The general

test procedure to verify current alarm operation will include simulating a

transducer input signal and varying this signal:

  1. to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
  2. to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
  3. to produce a nonalarm condition.

3500/15-02-00-00 Direct

  1. Disconnect PWR, COM, and SIG field wiring from the channel terminals on

the I/O module.

  1. Connect test equipment and run software as described in Section 5.1.5.5
  2. (Test Equipment and Software Setup – Thrust Position and Differential

    Expansion).

    1. Adjust the power supply to produce a voltage that is within the Direct

    setpoint levels on the Direct bar graph display of the Verification screen.

    1. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

    OK LED is on, the bar graph indicator for Direct is green, and the Current

    Value field has no alarm indication.

    1. Adjust the power supply voltage such that the signal just exceeds the

    Direct Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the

    alarm time delay expires and verify that the bar graph indicator for Direct

    changes color from green to yellow and that the Current Value Field

    indicates an Alarm.

    1. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

    bar graph indicator for Direct remains yellow and that the Current Value

    Field still indicates an Alarm.

    1. Adjust the power supply such that the signal just exceeds the Direct Over

    Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm

    time delay expires and verify that the bar graph indicator for Direct

    changes color from yellow to red and that the Current Value Field

    indicates an Alarm.

    1. Press the RESET switch on the Rack Interface Module (RIM). Verify that the

    bar graph indicator for Direct remains red and that the Current Value Field

    still indicates an Alarm.

    1. Adjust the power supply voltage such that the signal reads below the Over

    Alarm setpoint levels. If the nonlatching option is configured, observe that

    the bar graph indicator for Direct changes color to green and that the

    Current Value Box contains no indication of alarms. Press the RESET

    switch on the Rack Interface Module (RIM) to reset latching alarms.

    1. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under

    Danger/Alarm 2 setpoints by adjusting the power supply to exceed the

    Under Alarm setpoint levels.

    1. If you can not verify any configured alarm, recheck the configured

    setpoints. If the monitor still does not alarm properly or fails any other

    part of this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).

    1. 3500/15-02-00-00 Disconnect the test equipment and reconnect the PWR, COM, and SIG field

    wiring to the channel terminals on the I/O module. Verify that the OK LED

    comes on and the OK relay energizes. Press the RESET switch on the Rack

    Interface Module (RIM) to reset the OK LED.

    1. Repeat steps 1 through 12 for all configured channels.

Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!

 

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen