3500/15-02-02-00The general approach for testing these parameters is to simulate the Thrust

Position and Differential Expansion signal with a power supply. The output values

are verified by varying the input DC voltage 3500/15-02-02-00 and observing that the correct results

are reported in the Verification screen on the test computer.

 

brand Product Name Product model Order No
BENTLY modular 3500/15-02-02-00 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1806092-3929

 

3500/15-02-02-00 If Upscale direction (Normal for Thrust, Long for Differential Expansion) is

toward the probe:

Full Scale =

(Zero Position Voltage) + (Transducer Scale Factor × Top Meter Scale)

Bottom Scale =

(Zero Position Voltage) – (Transducer Scale Factor × ABS (Bottom Meter

Scale)

Example 1:

3500/15-02-02-00 Transducer scale factor = 200 mV/mil

Meter scale range = 25-0-25 mil

Zero Position Voltage = -9.75 Vdc

Full Scale Value = (-9.75) + (0.200 × 25)

= -4.75 Vdc

Bottom Scale Value = (-9.75) – (0.200 × 25)

= -14.75 Vdc

Example 2:

Transducer scale factor = 7,874 mV/mm

Meter scale range = 1-0-1 mm

Zero Position Voltage = -10.16 Vdc

Full Scale Value = (-10.16) + (7.874 × 1)

= -2.286 Vdc

Bottom Scale Value = (-10.16) – (7.874 × 1)

= -18.03 Vdc

If Upscale direction (Normal for Thrust, Long for Differential Expansion) is away

from the probe:

Full Scale =

(Zero Position Voltage) – (Transducer Scale Factor × Top Meter Scale)

Bottom Scale =

(Zero Position Voltage) + (Transducer Scale Factor × ABS(Bottom Meter

Scale)

Example 1:

3500/15-02-02-00 Transducer scale factor = 200 mV/mil

Meter scale range = 25-0-25 mil

Zero Position Voltage = -9.75 Vdc

Full Scale Value = (-9.75) – (0.200 × 25)

= -14.75 Vdc

Bottom Scale Value = (-9.75) + (0.200 × 25 )

= -4.75 Vdc

Example 2:

Transducer scale factor = 7,874 mV/mm

Meter scale range = 1-0-1 mm

Zero Position Voltage = -10.16 Vdc

Full Scale Value = (-10.16) – (7.874 × 1)

= -18.03 Vdc

Bottom Scale Value = (-10.16) + (7.874 × 1)

= -2.286 Vdc

  1. Adjust the power supply voltage to match the voltage displayed in the Z.P.

Volts box. The Direct bar graph display and the Current Value Box should

read 0 mil (0 mm) ±1 %.

  1. Adjust the power supply voltage for the calculated full scale. Verify that

the Direct bar graph display and the Current Value Box is reading ±1 % of

full scale. If the recorder output is configured, refer to Section 5.1.9 (Verify

Recorder Outputs) for steps to verify the recorder output.

  1. Adjust the power supply voltage for the calculated bottom scale. Verify

that the Direct bar graph display and the Current Value Box is reading ±1

% of bottom scale. If the recorder output is configured, refer to Section

5.1.9 (Verify Recorder Outputs) for steps to verify the recorder output.

  1. If the reading does not meet specifications, check that the input signal is

correct. If the monitor still does not meet specifications or fails any other

part of this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).

  1. 3500/15-02-02-00 Disconnect the test equipment and reconnect the PWR, COM, and SIG field

wiring to the channel terminals on the I/O module. Verify that the OK LED

comes on and the OK relay energizes. Press the RESET switch on the Rack

Interface Module (RIM) to reset the OK LED.

  1. Repeat steps 1 through 8 for all configured channels.

Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!

 

Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen