Description
3500/15-03-00-00 The following sections describe how to test alarms, verify channels, and test OK
limits for channels configured as Eccentricity. The output values and alarm
setpoints are verified by varying the input Eccentricity signal level (both peak to
peak amplitude and DC voltage bias) and 3500/15-03-00-00 observing that the correct results are
reported in the Verification screen on the test computer.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/15-03-00-00 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1806092-3929 |
- 3500/15-03-00-00 The general approach for testing alarm setpoints is to simulate the eccentricity
signal with a function generator and power supply. The alarm levels are tested by
varying the output from the test equipment and observing that the correct results
are reported in the Verification screen on the test computer. It is only necessary
to test those alarm parameters that are configured and being used. The general
test procedure to verify current alarm operation will include simulating a
transducer input signal and varying this signal:
-
- to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
- to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
- to produce a nonalarm condition.
Peak to Peak
- Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
- Connect test equipment and 3500/15-03-00-00 run software as described in Section 5.1.6.1
(Test Equipment and Software Setup – Eccentricity).
- Adjust the function generator amplitude such that the signal level does not
exceed any setpoint value for the pp mil bar graph.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for pp is green, and the Current Value
field has no alarm indication.
- Adjust the function generator amplitude such that the signal just exceeds
the pp Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for pp
changes color from green to yellow and that the Current Value Field
indicates an Alarm.
- 3500/15-03-00-00 Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for pp remains yellow and that the Current Value Field
still indicates an Alarm.
- Adjust the function generator amplitude such that the signal just exceeds
the pp Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after
the alarm time delay expires and verify that the bar graph indicator for pp
changes color from yellow to red and that the Current Value Field
indicates an Alarm.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for pp remains red and the Current Value Field still
indicates an Alarm.
- Adjust the function generator amplitude such that the signal reads below
the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for pp changes color to green and
that the Current Value Box contains no indication of alarms. Press the
RESET switch on the Rack Interface Module (RIM) to reset latching alarms.
- If you can not verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other
part of this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
- Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. 3500/15-03-00-00 Press the RESET switch on the Rack
Interface Module (RIM) to reset the OK LED.
- Repeat steps 1 through 11 for all configured channels.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen