3500/15 125840-02 The following recommendations are offered, but applicable safety codes for your area or equipment
type should also be consulted. The baseplate’s metal back must be grounded using a separate
conductor; the baseplate mounting screws are not considered to be an acceptable ground
connection by themselves. Use a minimum AWG #12 (3.3 mm2) wire with a ring terminal and star
lock washer under the head of one of the baseplate’s 3500/15 125840-02 two lower mounting holes. These two holes
have openings to the side to allow connecting a wire and ring terminal under the head of a
mounting screw. Connect the other end of this ground wire to a tapped hole in the panel that the
baseplate is mounted to, using a machine screw, 3500/15 125840-02 star lock washer, and flat washer. Alternately, if
your panel has a ground stud, it is recommended you use a nut and star lock washer for each wire
on the ground stud to ensure adequate grounding. Where connections are made to a painted panel,
the paint should be removed so clean, bare metal is exposed at the connection point. Terminals and
hardware used should be compatible with the aluminum baseplate material.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/15 125840-02 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1806092-3929 |
3500/15 125840-02 All baseplates grouped together in a Series 90-30 PLC system must have a common ground
connection. This is especially important for baseplates that are not mounted in the same control
cabinet.
3500/15 125840-02 Grounding 19” Rack-Mounted Baseplates
There are two Adapter Brackets choices for mounting a 10-slot Series 90-30 baseplate to a 19”
Rack. Regardless of which of the two Adapter Brackets is used, the 19” Rack should be
grounded as per the instructions in “System Grounding Procedures” section. (For details on the
Adapter Brackets, 3500/15 125840-02 see the “Mounting a Baseplate to a 19” Rack” section earlier in this chapter.)
Nineteen-Inch rack-mounted PLC baseplates should be grounded according to the guidelines in
the “Baseplate Safety Grounding” section, using a separate ground wire from the PLC baseplate
as shown in the previous figure.
If using the Recessed Mount Adapter Bracket (IC693ACC313), the ground wire can be
installed as shown in Figure 2-11 with the ground attached to the Recessed Mount Adapter
Bracket. An additional ground wire connecting the Adapter Bracket to a solid chassis
ground on the 19” Rack should be installed. Use the same or equivalent hardware and
paint removal scheme as shown in the previous figure.
If using the Surface Mount Adapter Bracket (IC693ACC308), the ground wire should be
run from the baseplate as shown in Figure 2-11, to a solid chassis ground on the 19” Rack.
Use the same or equivalent hardware and paint removal scheme as shown in the previous
figure.
Programmer Grounding
For proper operation, a computer (programmer) running PLC software must have a ground
connection in common with the applicable baseplate when connecting to a CPU or intelligent
module such as a PCM or DSM. Normally, this common ground connection is provided by
ensuring that the programmer’s power cord is connected to the same power source (with the
same ground reference point) as the baseplate. If the programmer ground is at a different
potential than the PLC ground, a shock hazard could exist. Also, damage to the ports or
converter (if used) could occur when the programmer serial cable is connected between the two.
If it is not possible to ensure this common ground scheme, use a port isolator (IC690ACC903)
between the programmer and PLC serial port connection, and avoid touching the programmer
and PLC at the same time.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen