3500/22-01-02-00 Twisted, shielded instrumentation cable is strongly recommended for analog module input or
output signal connections. Proper grounding of the shield is also important. For maximum
electrical noise suppression, the cable shield should only be grounded at one end of the cable.
For Input modules, it is generally preferable to ground the end that is in the noisiest
environment (usually the field device end). 3500/22-01-02-00 For Output modules, ground at the module end.
See Chapters 10 (Analog Input), 11 (Analog Output), and 12 (Analog Combination) for
additional wiring information for specific modules.
Connections to an Analog module from user 3500/22-01-02-00 devices are made to screw terminals on a
removable 20-terminal connector block mounted on the front of the module. Actual terminals
used are shown in the specifications for the individual modules.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/22-01-02-00 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1806092-3929 |
3500/22-01-02-00 The following methods are, for most applications, the preferred methods. However, in some
applications, alternate methods may be used successfully. The examples shown later in this
section discuss and illustrate a variety of possible wiring arrangements.
3500/22-01-02-00 Using a Terminal Strip
Mount a terminal strip inside the control enclosure and run a shielded cable from the
terminal strip to each input circuit on the module’s terminal board terminals.
Connect each cable’s shield to one point on the metal panel next to the terminal strip.
When attaching to a painted surface, first remove the paint around the tapped hole and use
an appropriate ring terminal, machine screw, lockwasher and flat washer. Do do not
connect the shields at the module end (cut shield off at module end of cable and insulate
with shrink tubing).
Wire the field device to the terminal strip with a shielded cable, 3500/22-01-02-00 grounding the shield at the
device end only (cut shield off at terminal strip end of cable and insulate with shrink
tubing). If attaching shields to a painted surface, first remove the paint around the
connection. Also, keep the length of exposed (outside of shield) leads at the terminal strip
and device ends as short as possible.
Direct Method
Run a shielded cable from the field device (transducer, potentiometer, etc.) directly to the
module.
Connect the conductors to the applicable screws on the module’s terminal board.
Ground the shield at the field device end, exposing a minimum amount of conductor to the
noisy environment. If attaching shields to a painted surface, first remove the paint around
the tapped hole and use an appropriate ring terminal, machine screw, lockwasher and flat
washer. Do not connect the shield at the module 3500/22-01-02-00 end (cut shield off at module end of cable
and insulate with shrink tubing).
TBQC Not Recommended for Analog Modules
The Terminal Block Quick Connect (TBQC) Assembly is not recommended for use with analog
modules due to cable shielding requirements.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 180 6092 3929
Mail: 2235954483@qq.com
Contact: Chen