Description
3500/92-04-01 The procedures for verifying channel values and corner frequencies require that
you use the following formulas to calculate the verification frequency.
Find the center of the Band-pass frequency range. Input the configured high
pass filter corner frequency and the 3500/92-04-01 low-pass filter corner frequency into the
formula below:
Frequency = (0.89 × HPF) + (0.1575 × LPF)
HPF = High-pass Filter Corner Frequency
LPF = Low-pass Filter Corner Frequency
If no filtering is configured, set the frequency of the function generator to 100 Hz.
brand | Product Name | Product model | Order No |
BENTLY | modular | 3500/92-04-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
3500/92-04-01 If a low-pass filter is configured and no high-pass filter is configured, use the
following to determine the HPF to use in the formula:
– If the units are integrated or rms, use a HPF of 10 Hz. For any other
configuration, use a HPF of 3 Hz.
If a high-pass filter is configured and no low-pass filter is configured, use the
following to determine the LPF to use 3500/92-04-01 in the formula:
– If the configuration is a single channel with no integration, use a LPF of
30 kHz.
– If the configuration is a single channel with integration, use a LPF of 14.5
kHz.
– If the configuration is a dual channel pair, 3500/92-04-01 use a LPF of 9.155 kHz.
The procedures for verifying channel values and corner frequencies required that
you use the following formulas to calculate the input voltage for full-scale. To
find the full-scale input voltage, use appropriate table for integrated or non
integrated units.
3500/92-04-01 The general approach for testing OK limits is to input a DC voltage and adjust it
above the Upper OK limit and below the Lower OK limit. This should cause a not
OK condition and cause the OK Relay to change state. The Upper and Lower
OK limits are displayed in the Verification screen on the test computer.
- Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
- Connect test equipment and run software as described in Section 5.1.9.1
(Test Equipment and Software Setup – Acceleration).
- Bypass all other configured channels.
- Adjust the power supply voltage to -7.00 Vdc.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
monitor OK LED is on and that the Channel OK State line in the Channel
Status section of the Verification Display screen reads OK.
- Verify that the OK relay on the Rack 3500/92-04-01 Interface I/O Module indicates OK
(energized). See 3500/20 Rack Interface Module manual, part #129768-01.
- Increase the power supply voltage (more negative) until the OK LED just
goes off (upper limit). Verify that the Channel OK State line on the
Verification screen reads not OK and that the OK Relay indicates not OK.
Verify that the Upper OK limit voltage displayed on the Verification screen is
equal to or more positive than the input voltage.
- Decrease the power supply voltage (less negative) to -7.00 Vdc.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED comes back on and the OK relay energizes. Verify that the Channel
OK State line in the Channel Status section reads OK.
- Gradually decrease the power supply voltage (less negative) until the OK
LED just goes off (lower limit). Verify that the Channel OK State line in the
Channel Status section reads not OK and that the OK Relay indicates not
- Verify that the Lower OK limit voltage displayed on the Verification
screen is equal to or more negative than the input voltage.
- Increase the power supply voltage (more negative) to -7.00 Vdc.
- Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED comes back on, the OK relay energizes, and the Channel OK State
line in the Channel Status section reads OK.
- If you can’t verify any configured OK limit, go to Section 5.1.11 (If a Channel
Fails a Verification Test).
- Disconnect the power supply and multimeter and reconnect the PWR, COM,
and SIG field wiring to the channel terminals on the Proximitor/Seismic I/O
Module. Press the RESET switch on the Rack Interface Module (RIM) and
verify that the OK LED comes on and the OK relay energizes.
- Repeat steps 1 through 14 for all configured channels.
- Return the bypass switch for all configured channels back to their original
setting
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the delivery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 181 0693 7731
Mail: 2872270648@qq.com
Contact: Chen