Description
The process of identifying the type of Power Supply and setting operating
parameters is called configuration. To configure a Power Supply, use this
section to gather configuration information, then use the Rack Configuration
Software to set the options and download the settings to the rack. The Rack
Configuration and Utilities Guide explains how to connect a computer to a rack
and run the Rack Configuration Software.
The Power Input Module is half-height and connects the power source to the
Power Supply. Install the Power Input Module behind the Power Supply (in a
Rack Mount or a Panel Mount rack) or above the Power Supply (in a Bulkhead
rack). For example, if the Power Supply is installed in the upper slot then it’s
Power Input Module must be installed in the upper slot. Removing or inserting a
Power Input Module will not disrupt operation of the 3500 rack as long as the
other Power Supply and its associated Power Input Module are installed.
AC Power Input Module (Low Voltage version)
Use the AC Power Input Module (Low Voltage version) when the rack will be
powered by low voltage AC (85 to 132 Vac, rms).
brand | Product Name | Product model | Order No |
BENTLY | modular | 125720-02 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
To avoid ground loops, the system must provide a single point ground. The
Power Input Modules come with a switch that lets you control where the system
is grounded. If two Power Supplies are installed then both switches need to be
set to the same position. A CLOSED switch grounds the system through the
GND terminal on the Terminal Strip connector. If the system is grounded at
another location, such as when internal/external barriers are used, you need to
be sure the switch is OPENED. The following figure and steps show how to set
the switch to the desired position. For most racks the switch will be set to
CLOSED at the factory; if Internal Barriers are installed at the factory the switch
will be set to the OPENED position.
1) When the switch is
pushed to this side the
switch is in the
CLOSED position.
2) When the switch is
pushed to this side the
switch is in the
OPENED position.
3) Grounding switch.
Depending on model,
this switch could be
located directly above or
below the input
connector.