Description
For systems with internal/external barriers, refer to the 3500
Field Wiring Diagram Package for grounding requirements.
1) Remove the line cord protection cover from the Terminal Strip connector.
2) Remove the Phillips screw from the side. The screw holds the sheet metal
cover on the Power Input Module.
3) Loosen the two screws that hold the Chassis ground clip. The screws are
located below the Terminal Strip connector. Remove the Chassis ground clip.
4) While disengaging the sheet metal tab on the bottom of the sheet metal
cover, slide the sheet metal cover over the Terminal Strip connector.
5) Slide the switch to the desired position.
6) Replace the cover and the Chassis ground clip on the Power Input Module.
brand | Product Name | Product model | Order No |
BENTLY | modular | 125736-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
This section shows how to verify that the Power Supplies and Power Input
Modules are operating correctly.
When performed properly, this module may be removed from the rack while
power is applied to the rack. Refer to the Rack Installation and Maintenance
Manual (part number 129766-01) for the proper procedure.
If a problem is detected with a Power Supply or a Power Supply has been
removed or installed, one of the following messages will be entered in the
System Event List:
Message
Description
Supply OK / Installed
A Power Supply has been installed or a Power
Supply has gone from a not OK condition to an
OK condition.
Supply Faulted /
Removed
A Power Supply has been removed or a Power
Supply has gone not OK.
If the Power Supply OK LED is off, check the following items:
1) Verify that the correct voltage is connected to the Power Input Module.
2) Verify that the installed Power Input Module matches the installed Power
Supply. For example, an AC Power Input Module with the AC version of the
Power Supply.
3) Check to see if the fuse on the Power Input Module has blown. If the fuse is
blown, replace it. A blown fuse may be due to:
- a) Severe over voltage on the Power Input Module.
- b) A fault within the 3500 Power Supply.
4) If steps 1 through 3 do not solve the problem:
- a) Install a new Power Supply. If the Power Supply OK LED comes on,
the original Power Supply is faulty.
- b) If the problem persists, the Power Input Module may be damaged.
Contact Bently Nevada Corporation.