Description
Take note of the following items when daisy chaining Rack Interface I/O
Modules:
ï Use the HOST port to connect to the host computer or to the rack in the
daisy chain that is closer to the host computer.
ï Use the RACK RS-422 port to connect to the rack that is farther from the
host computer.
ï Use the following cables for the connection between the racks in the
daisy chain:
– For lengths of 150 meters (500 ft) or less, use cable
130122-XXXX-XX (PVC Insulation) or cable 131107-XXXX-XX
(TeflonÆ Insulation).
– For lengths greater than 150 meters (500 ft), use one cable
130122-XXXX (PVC Insulation) or cable 131107-XXXX-XX
(TeflonÆ Insulation) along with as many RS-422 extension cables
130121-XX-XX (150 meters (500 ft) standard length) to create a
cable up to 1220 meters (4000 ft) in length.
brand | Product Name | Product model | Order No |
BENTLY | modular | 129478-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
To remove a terminal block from its base, loosen the screws attaching the
terminal block to the base and then grip the block firmly and pull. Do not pull the
block out by its wires because this could loosen or damage the wires or
connector.
Refer to the 3500 Field Wiring Diagram Package for the recommended wiring.
Also, do not remove more than 6 mm (0.25 inches) of insulation from the wires.
Data Manager I/O Modules
The Data Manager I/O Module must be installed behind the Power Supplies
between the Power Input Modules and the Rack Interface I/O Module (in a Rack
Mount or Panel Mount rack) or above the Power Supplies between the Power
Input Modules and the Rack Interface I/O Module (in a Bulkhead rack). The
function of the Data Manager I/O module is to connect the 3500 rack to TDIX or
DDIX Communication Processors. Each port can connect up to 24 channels,
from the 3500 rack to the Communication Processor. Refer to the table on page
9 for the different options that are available.
1) Used to transfer the static information from
Port 1 of this 3500 rack to the static connector
on the Communication Processor.
2) Used to transfer the dynamic information from
Port 1 of this 3500 rack to the dynamic
connector on the Communication Processor.
3) Used to transfer the information from Port 2 of
this 3500 rack to the static connector on the
Communication Processor.
4) Used to transfer the dynamic information from
Port 2 of this 3500 rack to the dynamic
connector on the Communication Processor.
Note: The 3500 Monitoring System supports the
DDIX and TDIX Communication Processors.
Note: The Data Manager I/O will cease to operate
if the Rack Interface Module is removed.