Description
Software Switches Reset
Event Number: 305
Event Classification: Potential Problem
Action: Download the software switches to the Rack Interface Module. If
the software switches are not correct, replace the Rack Interface
Module as soon as possible.
Init Real Time Clock (Initialize Real Time Clock)
Event Number: 306
Event Classification: Potential Problem
Action: Replace the Rack Interface Module as soon as possible.
Monitor TMR PPL Failed (Monitor TMR Proportional value Failed)
Event Number: 310
Event Classification: Potential Problem
Action: Replace the monitor installed in the slot as soon as possible.
Monitor TMR PPL Passed (Monitor TMR Proportional value Passed)
Event Number: 311
Event Classification: Potential Problem
Action: Replace the monitor installed in the slot as soon as possible.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.
Module Removed from Rack
Event Number: 325
Event Classification: Typical Logged Event
Action: No action required.
Module Inserted in Rack
Event Number: 326
Event Classification: Typical Logged Event
Action: No action required.
Supply OK/Installed
Event Number: 330
Event Classification: Potential Problem
Action: Determine if a power supply has been installed. Verify that there is
not a problem with the power source. If there are no problems with
the power source, replace the power supply as soon as possible.
brand | Product Name | Product model | Order No |
BENTLY | modular | 133434-01 | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
Supply Faulted/Removed
Event Number: 331
Event Classification: Potential Problem
Action: Determine if a power supply has been removed. Verify that there
is not a problem with the power source. If there are no problems
with the power source, replace the power supply as soon as
possible.
Rack/RIM Powered Down (Rack or Rack Interface Module Powered Down)
Event Number: 340
Event Classification: Typical Logged Event
Action: No action required.
Rack/RIM Powered Up (Rack or Rack Interface Module Powered Up)
Event Number: 341
Event Classification: Typical Logged Event
Action: No action required.
Modem Reinitialized
Event Number: 350
Event Classification: Typical Logged Event
Action: No action required.
Device Events Lost
Event Number: 355
Event Classification: Typical Logged Event
Action: No action required.
Module Alarms Lost
Event Number: 356
Event Classification: Typical Logged Event
Action: No action required.
Rack Time Changed
Event Number: 360
Event Classification: Typical Logged Event
Action: No action required.
Module Entered Calibr. (Module Entered Calibration Mode)
Event Number: 365
Event Classification: Typical Logged Event
Action: No action required.
Module Exited Calibr. (Module Exited Calibration Mode)
Event Number: 366
Event Classification: Typical Logged Event
Action: No action req
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact Us:+86 18106937731
Whatapp:+86 15359293870
Email: geabbdcs@gmail.com / 2872270648@qq.com
Contact Person: Chen