Description

Event Number: 148

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the

problem. If the problem is not caused by noise, check to see if

one of the following components is faulty:

– the Monitor Module

– the Power Supply installed in the upper slot

– the Power Supply installed in the lower slot

Monitor Module will stop alarming.

Pass Transducer Power

Event Number: 149

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the

problem. If the problem is not caused by noise, check to see if

one of the following components is faulty:

– the Monitor Module

– the Power Supply installed in the upper slot

– the Power Supply installed in the lower slot

* Fail I/O Board +2.5V-AB (Fail I/O Board +2.5V – upper and lower Power

Supplies)

Event Number: 150

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the

problem. If the problem is not caused by noise, check to see if

one of the following components is faulty:

– the Monitor Module

– the Power Supply installed in the upper slot

– the Power Supply installed in the lower slot

Monitor Module will stop alarming.

Pass I/O Board +2.5V-AB (Pass I/O Board +2.5V – upper and lower Power

Supplies)

Event Number: 151

Event Classification: Severe/Fatal Event

Action: Verify that noise from the power source is not causing the

problem. If the problem is not caused by noise, check to see if

one of the following components is faulty:

– the Monitor Module

– the Power Supply installed in the upper slot

– the Power Supply installed in the lower slot

 

brand Product Name Product model Order No
BENTLY modular 135489-04 nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1810693-7731

 

Device Configured

Event Number: 300

Event Classification: Typical Logged Event

Action: No action required.

* Configuration Failure

Event Number: 301

Event Classification: Potential Problem or Severe/Fatal Event

Action: Download a new configuration to the Monitor Module. If the

problem still exists, replace the Monitor Module immediately.

Monitor Module will stop alarming.

* Module Entered Cfg Mode (Module Entered Configuration Mode)

Event Number: 302

Event Classification: Typical Logged Event

Action: No action required.

Monitor Module will stop alarming.

Software Switches Reset

Event Number: 305

Event Classification: Potential Problem

Action: Download the software switches to the Monitor Module. If the

software switches are not correct, replace the Monitor Module as

soon as possible.

Monitor TMR PPL Failed (Monitor TMR Proportional Value Failed)

Event Number: 310

Event Classification: Potential Problem

Action: Verify that the transducer is properly installed. If the transducer is

properly installed, check to see if one of the following components

is faulty:

– the Transducer

– the Tachometer I/O Module

– the Monitor Module

Monitor TMR PPL Passed (Monitor TMR Proportional Value Passed)

Event Number: 311

Event Classification: Potential Problem

Action: Verify that the transducer is properly installed. If the transducer is

properly installed, check to see if one of the following components

is faulty:

– the Transducer

– the Tachometer I/O Module

– the Monitor Module