GE General Electric Technical Specifications: IS200VVIBH1BBA
IS200VVIBH1BBA Indications and Operations are as outlined under Phase Time Overcurrent 1.
Blocking From Logic Inputs:
- Inject voltage and current above minimum at a frequency to cause a pickup.
- Assert a logic input to provide a “Block Underfreq 1 (2)”. The PICKUP indicator should immediately go out.
- Repeat steps 1 and 2 for logic input “Block 1 TRIP Relay” as required.
IS200VVIBH1BBA Timing:
- Connect the “Stop Trigger.”
- Set the voltage source prefault mode to nominal voltage, current and frequency.
- Set the voltage source fault mode to nominal voltage and current, but with a frequency below pickup.
- Set the source to prefault mode, reset the timer, and apply to the relay.
- Jump the source to fault mode and measure the operating time.
- Repeat steps 4 and 5 four more times and obtain an average of the time intervals.
- Reset the relay and disconnect the “Stop Trigger.”
brand | Product Name | Product model | Order No |
GE Fanuc | Module card | IS200VVIBH1BBA | nothing |
Place of Origin | Marketable land | Imported or not | defects liability period |
Europe and America | Nationwide and overseas | yes | a year |
Place of shipment | Delivery method | How to use | Applicable industries |
Xiamen | Shunfeng Express | Commissioning and installation | Power Plant Steel Plant Cement Plant Shipboard Papermaking |
Service advantages | Foreign import, goods preparation and supply | Reasonable price and reliable quality | Pictures are for reference only |
Product features | Primary source of goods, supply by model | After sales guarantee | Chen 1810693-7731 |
Test Connections per Figure 17–1: RELAY TEST WIRING – WYE CONNECTION or Figure 17–2: RELAY
TEST WIRING – DELTA CONNECTION on page 17–4.
Procedure To Check:
IS200VVIBH1BBA Minimum Operating Voltage Supervision:
- Inject voltage into the Va bus voltage input at a level well below the Minimum Operating Voltage level. Also
inject Ia = Ib = Ic at a level well above the Minimum Operating Current level. Starting with the Va frequency
at a level well below the Frequency Decay Pickup, drop the frequency of Va at a speed greater than the
IS200VVIBH1BBA FREQUENCY DECAY RATE setting. The pickup indicator should remain off.
- Inject voltage into the Va bus voltage input at a level well above the Minimum Operating Voltage level. Also
inject Ia = Ib = Ic at a level well above the Minimum Operating Current level. Starting with the Va frequency
at a level well below the Frequency Decay Pickup, drop the frequency of Va at a speed greater than the
IS200VVIBH1BBA FREQUENCY DECAY RATE setting. The pickup indicator should come on while the Va frequency is dropping.
Minimum Operating Current Supervision:
- Inject voltage into the Va bus voltage input at a level well above the Minimum Operating Voltage level. Also
inject Ia = Ib = Ic at a level well below the Minimum Operating Current level. Starting with the Va frequency
at a level well below the Frequency Decay Pickup, drop the frequency of Va at a speed greater than the
FREQUENCY DECAY RATE setting. The pickup indicator should remain off.
- With the Va voltage at a level well above the Minimum Operating Voltage level, increase Ia to a level well
above the Minimum Operating Current level. Currents Ib and Ic should be well below the Minimum Operat
ing Current level. Starting with the Va frequency at a level well below the Frequency Decay Pickup, drop
the frequency of Va at a speed greater than the FREQUENCY DECAY RATE setting. The pickup indicator
should come on while the Va frequency is dropping.
- With the Va voltage at a level well above the Minimum Operating Voltage level, increase Ib to a level well
above the Minimum Operating Current level. Currents Ia and Ic should be well below the Minimum Operat
ing Current level. Starting with the Va frequency at a level well below the Frequency Decay Pickup, drop
the frequency of Va at a speed greater than the FREQUENCY DECAY RATE setting. The pickup indicator
should come on while the Va frequency is dropping.
- With the Va voltage at a level well above the Minimum Operating Voltage level, increase Ic to a level well
above the Minimum Operating Current level. Currents Ia and Ib should be well below the Minimum Operat
ing Current level. Starting with the Va frequency at a level well below the Frequency Decay Pickup, drop
the frequency of Va at a speed greater than the FREQUENCY DECAY RATE setting. The pickup indicator
should come on while the Va frequency is dropping.
Why are the prices of many products of our company more competitive?
(1) Source purchase to reduce the price difference in the intermediate phase
(2) Stable channel and more guaranteed supply
Lead time problem
(1) For the spot products in stock, the de
livery can be arranged on the same day after the contract payment is signed
(2) Order products and deliver according to the quoted delivery date
Xiamen Xiongba adheres to the enterprise philosophy of “improving the value of spare parts supply chain”,
For the simple purchase procedure of spare parts, ensure that they are delivered to the site in a timely manner, and help users reduce the risk of downtime caused by the shortage of spare parts
The emergency spare parts support service is complete, and the user can customize the spare parts. The quality of the spare parts is reliable. All the spare parts provided enjoy a one-year super long warranty
Spot stock, fast response, reduce user capital investment, improve spare parts utilization, spare parts replacement!
Details: If you need urgent delivery orders, please feel free to contact us, and we will try our best to meet your needs.
Price problem: If you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.
Contact us:+86 181 0693 7731
Mail: 2872270648@qq.com
Contact: Chen