Product name:HIMA F8628X Digital output module power supply

Product model:F8628X

The F8628X I/O module is used for signal transmission and matching between the factory and the central module. The input and output circuits are always input into the I/O module through the front cable plug.

40 in stock

Category: SKU: F8628X
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

In the subrack, F8628X slots 4 to 15 are provided for the input/output modules. Any arrangement of I/O module types is possible. In PES with redundant I/O bus, the modules on slots 4 to 9 are assigned to the 1st I/O bus and 10 to 15 to the 2nd I/O bus.

 

Slots 1 to 3 hold the power distribution modules F 7133. The power distribution module F 7133 can be used to fuse the modules as well as the sensors and the actors. They are non-interactive and have a fuse monitoring for fuse fail by means of a LED and a contact.

There is a cable tray under the subrack. It is equipped with a receptable for the lable which can be hinged to provide easy access to the cables.

 

brand Product Name Product model Order No
HIMA modular F8628X nothing
Place of Origin Marketable land Imported or not defects liability period
Europe and America Nationwide and overseas yes a year
Place of shipment Delivery method How to use Applicable industries
Xiamen Shunfeng Express Commissioning and installation Power Plant Steel Plant Cement Plant Shipboard Papermaking
Service advantages Foreign import, goods preparation and supply Reasonable price and reliable quality Pictures are for reference only
Product features Primary source of goods, supply by model After sales guarantee Chen 1810693-7731

 

F8628X Standard solution: The 24 V power L+ is distributed via a plug-in fusing and power distribution unit (refer to the HIMA articles). A 16 A back-up fuse is provided. The power for the input/output modules is fed in at the backside to the slots of the power distribution modules via XG.6/7/8. Each I/O module is related to a fuse on the module F 7133 (refer also to the description of the assembly kit B 4…). The supply of the I/O modules is either via the cable plug on the front side or via the connection already integrated in the I/O busboard (for (Ex)i modules and partly analog input modules).

 

The relation between the power distribution modules with 4 fuses and the slots of the I/O modules is as follows:

F 7133 in slot 1 supplies I/O slots 4 … 7

F 7133 in slot 2 supplies I/O slots 8 … 11

F 7133 in slot 3 supplies I/O slots 12 … 15

 

L- is also taken from the plug-in power distribution unit to be connected to the potential distributor XG. 14. So all power distribution modules F 7133 are internal connected with L-. Via the front side of the power distribution modules the L- is also fed to the input/output modules via the cable plugs.

 

The circuit feeding the sensors is connected via the front to the F 7133 module. It is advisable to supply the input module and the appertaining sensors via the same circuit of the power distribution module F 7133.