NPBU-42C ABB Programmable Logic Controller for Distributed Control System

Numer modelu: NPBU-42C

Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 9
Port isolation: 120 VDC
Weight : 3Kg
Shipping Weight : 4 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number NPBU-42C
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

Enclosure: Plastic, dimensions: 45 mm x 75 mm x 105 mm. Degree of
protection: IP 20
Mounting: Onto a standard mounting rail
Hardware settings:
• Six DIP switches for setting the node number. Allocated node
numbers: module 1 = 2 (default), module 2 = 3, module 3 = 4.
Maximum: 63
• One DIP switch for enabling/disabling digital input DI1 hardware
filtering. Default: filtering on
Connectors:
• Light transmitter and receiver (Hewlett-Packard Versatile Link) for
ACS 600 connection
• Two screw terminal blocks (Phoenix Contact MVBSTW 2,5/8-ST5,08) for digital I/O and power supply connections. Conductor crosssectional area: 0.5 to 2.5 mm2
Digital inputs 1 and 2:
• Voltage range: ±24 to 250 V d.c., 110 to 230 V a.c. ±10%
• Input current: 10 mA at 24 V d.c., 4 mA max. at 115/230 V a.c.
• Logical thresholds (d.c.): “1” > 12 V, “0” < 8 V
• Logical thresholds (a.c.): “1” > 40 V, “0” < 20 V
• Isolated from each other and the power supply.
Test voltage: 4 kV a.c., 1 minute
• Hardware filtering time: max. 10 ms
(Can be disabled for digital input 1)
Relay outputs 1 and 2:
• Max. voltage: 120 V d.c., 250 V a.c.
• Switching capacity: 8 A at 24 V d.c. (resistive load),
0.4 A at 120 V d.c. (resistive load), 2000 VA at 250 V a.c.
• Max. continuous current: 2 A RMS
• Contact material: Silver cadmium oxide (AgCdO)
• Contact protection: Varistor (250 V). With an inductive load, an
external protective component should be installed at the load end
• Isolated from each other and the power supply.
Test voltage: 4 kV a.c., 1 minute
General:
• Current consumption: 50 mA at 24 V d.c
• All materials are UL/CSA approved
• Fast transient burst immunity (IEC 801-4): 4 kV 5/50 ns
• Electromagnetic emissions: In accordance to EN 55022 B